Tecnoware Power Systems
EVO STAR 10-50
48
ELECTRICAL DATA
SIZE in KVA
10
15
20
30
40
50
Active power
8
12,5
16
24
32
40
Efficiency Ac/Ac 100%
load
90,5
90,6
90,7
90,9
91
91,1
Noise @ 7mt dB(A)
52
52
54
54
57
57
Output current @ 400V
cos phi 0,8
14,45
21,68
28,90
43,35
57,8
72,5
Rectifier
Configuration
Tiristor bridge full control
Nominal voltage
380-400-415Vac, three phase +N+P.E.
Frequency
50/60 Hz, +/- 10% selectable
Power factor
0,85 inductive @ 100% load @ 400Vac
Tolerance on VDC
+/- 1%
Ripple on VDC
<1%
Max charging batteries
current
5
5
5
10
10
15
Battery
Rated buffer charge @ 20° 436V
Voltage discharge
320VDC (adjustable)
Inverter
Configuration
Three phase bridge IGBT with PWM control
Nominal output voltage
380-400-415Vac, trN+P.E.
Transformer
Standard
Wave form
Sinusoidal
Output voltage
tolerance
Static stability
+/-1%
Load variation 0%-100%-
0%
static stability in 40ms
Load variation 0%-50%-
0%
+/-3% static stability in 40ms
100% unbalance load
(IEC62040)
+/-3%