Tecnoware Power Systems
EVO STAR 10-50
41
Fasten the board as specified in picture 20 (named PCB2000 A14Rxx), to the supports
you have just inserted.
Create a connection with the supplied flat-cable between connector A (picture 20) and
connector CN3 on the relay board (picture 18), respecting polarity, that is to say, the
coloured wire level with the sign on the board (picture 22).
Picture 22
Position the remote panel in the place chosen for monitoring.
Proceed to connect power supply (220-240V/50-60Hz) to the M3 connector of the
PCB2000 A16Rxx board (picture 23), remembering to leave the central terminal free.
Carry out connection between interface connector indicated with the letter B (picture
20) and the M1 connector in picture 23. Bear in mind that the connection must be
carried out symmetrically (pin1-pin14, pin2-pin13, . . ., pin13-pin2, pin14-pin1).
Close the U.P.S second access by fastening the screws.
Continue the starting procedure (chapter 4) (if already operative restore functioning from U.P.S
by-pass following the instructions in paragraph 5).
Picture 23