Tecnoware Power Systems
EVO STAR 10-50
30
Chart 1
Panel check functions can be split into three main categories:
1.
Monitoring
2.
Diagnostic tools
3.
Functioning mode configuration
Led Associated element
Colour
Meaning
green
Back-up mains OK
Breaker is off (
where is
foreseen
)
red
Incorrect input voltage
Incorrect frequency
A
Back-up mains supply
flashing
Not synchronised
green
Rectifier mains OK
red
Rectifier mains alarmed
B
Rectifier mains supply
flashing
Incorrect cyclical sense
green
Rectifier OK
Rectifier alarmed
C
Rectifier
red
Rectifier off
green
battery OK
red
Battery alarmed
D
Battery
flashing
Battery discharging
green
inverter OK
Inverter alarmed
red
inverter off
E
Inverter
flashing
inverter current over 125%
green
Static commutator on
inverter
yellow
Static commutator on back-
up
F
Static commutator
red
Static commutator off or
blocked
green
Output voltage OK
Incorrect output voltage
red
Opened breaker
G
Output voltage
flashing
Output current over the
nominal value
green
Manual by-pass open
H
By-pass
red
Manual by-pass closed