6.4.2
INSTALLING THE REMOTE PANEL WITH E.P.O.
CAUTION! : FOLLOW THE INSTRUCTIONS VERY CAREFULLY. ANY
MISTAKE WILL CAUSE AN OUTPUT VOLTAGE DROP.
To carry out the installation of a remote panel with E.P.O., you must first carry out all
installation procedures for the normal remote panel, as in paragraph 6.4.1 then check the
actual efficiency of the remote panel by checking that the leds respect the colours on the
control panel.
After doing so please carry out the following instructions:
Make sure that the U.P.S. is off and that all the switches are off (if the U.P.S. is already
operative please proceed to by-pass setting chapter 5)
Unscrew the set screws from the second access panel of the U.P.S. and remove it.
Using cutting nippers cut the jumper as shown on the relay board (picture 18)
Turn on the “Reserve switch” disconnecting switch, the message “UPS Off” will appear on the
display and all the synoptic leds will turn red except for led “H” which will be green; wait till
led “A” (picture 17) starts flashing
Turn on the “Main switch” disconnecting switch, led “B”(picture 17) will turn green
Press the
button for about two seconds, the message “Starting up procedure started”, and
if the procedure has been carried out correctly led “C” (picture 17) and led “E” will turn green
in sequence and the message “UPS alarmed” will appear on the display
Press keys F6+F3 with the arrows F7-F8 select “Level of EPO”, press F6 to confirm, select
“Stop completed” and press F6.Press F3 to go back to the main menu
Press the E.P.O. switch on the remote panel and check that the emergency button actually
works (leds C, E, F picture 17) chapter 6.1 must turn red and the message (Emergency EPO
block) will appear
Reset the switch
Continue the starting procedure (chapter 4) (if already operative restore functioning from U.P.S
by-pass following the instructions in paragraph 5)