IO-iPOS4808 Technical Reference
Table 3.3
Jumper setting for the seven voltage levels of AxisID2
Level
Connection needed
Jumper
14
Jumper
13
L0
Connect input directly to ground
1-2
2-3
L1
Connect input through a 4.7K
Ω
resistor to ground
2-3
2-3
L2
Connected input through a 22K
Ω
resistor to ground
OFF
2-3
L3
Nothing connected
–
leave input open
-
OFF
L4
Connect input through a 22K
Ω
resistor to +5V
DC
OFF
1-2
L5
Connect input through a 4.7Kohm resistor to +5V
DC
2-3
1-2
L6
Connect input directly to +5V
1-2
1-2
The CAN protocol selection is done via AxisID2:
CANopen mode, if the input levels are: L0, L1 or L2
TMLCAN mode, if the input levels are L3, L4, L5, L6
Remark:
In CANopen mode, if the AxisID is set to 255, the drive remains “non
-
configured” waiting
for a CANopen master to configure it using CiA-
305 protocol. A “non
-
configured” drive answers
only to CiA-305 commands. All other CANopen commands are ignored and transmission of all
other messages (including boot-up) is disabled.