Standard connections - Port 6:
Encoder connection
Note - where a Technolog 120651763
('BH8') cable is attached to this
connector then the terminations are as
above.
Connector inputs - Encoder 1
Pin
Function
1200651763
'BH8'
2
DATA1 / PULSE1
Brown
8
PWR1 / CLK1
Red
7
GND
Blue
Connector inputs - Encoder 2
Pin
Function
1200651763
'BH8'
6
DATA2 / PULSE2
Pink
4
PWR2 / CLK2
Yellow
5
GND
Grey
Connector inputs - State1
Pin
Function
1200651763
'BH8'
1
STATE1
White
3
GND
Green
The optional open-face sealed, polarised / keyed, M12 'A' coded 'encoder' female connector is provided for the
attachment of external equipment with an 'encoder' interface - the following encoder protocols are supported by Cello 4S
(contact Technolog for further details).
Sensus / Invensys: UI-1203 (fixed field "R..." format, partial support for the variable "V..." format
Schlumberger / Neptune: E-Coder 6 digit / ProRead
Kent / Elster "K..." string format
Typical connections:
Refer to the "Standard connections - Port 4: Encoder connection" section of this document for further details.
Note
Refer also to the "Standard connections: Channel mapping & channel shadowing" section of this document
o
o
o
•
The 'Encoder' connection is only located at
Port 6 where either an internal or external
presure sensor is also required (for further
details refer to the "Standard connections
- Port 4: Internal pressure sensor" or
"Standard connections - Port 4: External
pressure sensor" sections of this document
as applicable).