C
Copyright Technolog Ltd. 2017. All rights reserved.
Information contained in this document subject to
change without prior notice.
Sheet 27 of 43
Technolog Limited,
Ravenstor Road,
Wirksworth,
DE4 4FY,
United Kingdom
T: +44 (0) 1629 823611
E: [email protected]
www.technolog.com
DMR No.: 7504
2099PM9000 Rev. B
Standard connections - Port 4:
Universal eight signal connection
(continued)
Input = Analogue, 4 to 20mA current (loop powered):
Input = Analogue, 4 to 20mA current (self powered):
Notes
1) For details of the required manual settings of the JP2-x and JP5 'dip switch' settings refer to the "Universal eight
signal input (4-20mA) 'dip switch' setting options" section of this document.
2) "Output 1" and "Output 2" are each capable of powering a maximum of 4x 4-20mA loops.
4 to 20mA
+V
GPi1 to GPi8
GND (0V)
+3V3
Output 1 or 2 (12V or 3V3)
VO+ (3V3)
+3V3
+12V
+V
GPi1 to GPi8
GND (0V)
+3V3
Output 1 or 2 (12V or 3V3)
VO+ (3V3)
+3V3
+12V
JP5 manual
'DIP' switch
= ON
4 to 20mA
Internal JP5
manual 'DIP'
switch = OFF
Internal JP2-x manual
'DIP' switch = ON
Internal 100
Ω
±
0.1%
precision resistor
enabled
Internal pull-down
resistor(s) enabled
in configuration file
330k
Ω
Internal debounce
capacitor(s) disabled
in configuration file
Internal pull-up
resistor(s) disabled
in configuration file
Internal JP2-x manual
'DIP' switch = ON
Internal 100
Ω
±
0.1%
precision resistor
enabled
Internal pull-down
resistor(s) enabled
in configuration file
330k
Ω
Internal debounce
capacitor(s) disabled
in configuration file
Internal pull-up
resistor(s) disabled
in configuration file