Menu Network
43
Speed stages of the outputs:
If the speed stages of an output are also to be captured, the digital value must have the same number
as the corresponding output, e.g., output 6 must have been allocated digital value 6. If the output is
allocated to another digital value, then status output still occurs (ON/OFF), but no speed stage output.
Heat meter:
The output variables of the heat meter function are
automatically bound into data records
accord-
ing to the sequence in the function list (heat meters 1 and 2 in data record 1, heat meters 3 and 4 in
data record 2). The values of the heat meter function cannot be defined as analogue values.
DATALOGGING
-----------------
DIGITAL VALUE 1:
Source: Output
1 : Solar pump1
Status: ON
DIGITAL VALUE 2:
Source: Output
2 : Solar pump2
Status: OFF
Digital values
– in this sub-menu the total 26 digital parameters of
the two data records are defined:
Data record 1: digital values 1 - 13
Data record 2: digital values 14 - 26
DATALOGGING
------------------
ANALOGUE VALUE 1:
Source: Input
1 : T.collector
Status: 105.6 °C
ANALOGUE VALUE 2:
Source: HTG CIRC.1
1 : Set flow temp.
Status: 58.2 °C
Analogue values
– in this sub-menu the total 32 analogue parame-
ters of the two data records are defined:
Data record 1: analogue values 1 - 16
Data record 2: analogue values 17 - 32
Functions of type "Heat meter" cannot be selected as
a source. Their parameters are automatically bound into the two
data records.
Delete All Def.
– is only displayed at expert level. All settings (definitions) in data logging can be
deleted by pressing the scroll wheel once. All logging values are in this respect set to
Source: User
<unused>
.
CAUTION!
Settings are immediately deleted without prior security prompt.
Important instruction re CAN data logging:
One controller (version > E3.18) or the C.M.I. must be
assigned node number 1 in the CAN network, so that the time stamp of this controller can be accept-
ed by other devices.