Heating circuit controller
61
AVERAGE of outdoor temperature
Sometimes, fluctuations in outdoor temperature may even not be desirable in calculation of flow
temperature or when determining the disconnection of the heating pump. Therefore, a separate calcu-
lation of the mean is available for the outdoor temperature to calculate the heating curve and the
disconnection of the pump. The following entries are found in this submenu:
HTG CIRC.1
for flow control:
Aver time: 10 min
The average outdoor temperature is calculated for 10 minutes
for the flow
T.outs.av.c: 13.6 °C
The current outdoor temperature average is 13.6°C
for shutdown:
Aver time: 30 min
The average outdoor temperature is calculated for 30 minutes
for switching off
T.ou.av.off: 13.8 °C
The current outdoor temperature average is 13.8°C
SHUTDOWN CONDITIONS and mixer behaviour
The controller allows the following switch-off conditions for the heating circuit pump:
if T.room
ACT > SET ? no
Hysteresis: 1.0 K
when the desired room temperature has been reached
If T.flow
SET < MIN ? yes
Hysteresis: 2.0 K
when the flow temperature falls below the lower limit T.FlowMIN
If T.outs.
Av.off> MAX ? no
T.outs.MAX: 20 °C
Hysteresis: 2.0 K
when the average outdoor temperature T.Out.MAX exceeds a
set value in the heating or lowering mode
If setback mode
and T.outside
ACT > MIN. ? no
T.outs.MIN: 5 °C
Hysteresis: 2.0 K
when the outdoor temperature T.Out exceeds a set value in the
lowering mode
If T.flow
ACT > MAX ? no
when the flow temperature is larger than T.FlowMAX (settings in
the heat curve) plus a fixed hysteresis of 3K, reactivation if
T.FlowACT. < T.FlowMAX
If heating circ. OFF
MIXER: close
Mixer behaviour:
In addition, in this menu you can determine
how the mixer is to respond once the pump has been switched
off (
close, open, unchanged, (continue to) control
).
If mixer enable is "OFF" the mixer remains stationary in the last
position it took up (Status Mixer: OFF).
The hystereses of the switch-off conditions generally have an
increasing
effect.
As both the outdoor temperature and the room temperature are taken into consideration when the set
flow temperature is calculated (provided a sensor is used), the best method is to switch off under the
limit T.flow MIN.