Profile function
84
Although the profile stage is registered every 6 hours in the internal storage, it gets lost while loading
new function data (load factory settings, load backup copy, data transfer from the C.M.I.).
If an internal cycle > 23.5 hours is set (such as heat drying of a pavement floor), profile stage 1 is
saved in the internal memory immediately after the profile function starts. This ensures that the heat
drying program continues to run when the controller is reconnected after a blackout just after the heat
drying of the floor pavement has been launched.
Example:
A temperature profile for heat drying of floor pavement is to be created. It is assumed that all input
variables are set to
User
so that the function can be manually changed at any time.
Entire menu view:
DES: PROFILE
INPUT VARIABLE:
OUTPUT VARIABLE:
FUNC.VAR: Temp.
The values are interpreted as temperature
cyclical:
no
No repeat after the profile has ended
Int. Sync: 24.0 Hrs
Switch to the next value every 24 hours
(Adjustment range 1 sec. to 48 hours)
START PROFILE
Press the scroll wheel to manually start the function
The following will appear when started:
STOP
PROFILE
(Display only if the input variable "Start Profile“ is set to
User
)
CURRENT STAGE: 3
SET VALUE: 26.0 °C
The set value of stage 3 is 26°C
Stage 1: 20 °C
Stage 2: 23 °C
Stage 3: 26 °C
Stage 4: 30 °C
Stage 5: 35 °C
Stage 6: OFF
No profile is active on the sixth day, output of the set value, if
Enable = OFF
Stage 7: 30 °C
Stage 8: 26 °C
Stage 9: 22 °C
if ENABLE = off
0.0 °C
If the profile mode has not been released, the module outputs
0°C
If the output variable "PROFILE ACTIVE" is now assigned to the heating circuit pump and the function
module "MIXER CONTROL" handles the set value, a pavement floor heat drying program has been
created for nine days. Here, make sure that a heating circuit control function does not simultaneously
control the output. To be on the safe side, set the enable for the heating circuit control function to
User OFF
during the process.