50
Parameter:
Data line:
Depending on the device type of the controller to be acquired, the following parameters are
available for visualisation:
Input: e0…ef (Inputs
1…16)
Output: a0…af
(Outputs
1…16)
Speed setting: d1, d2, d6, d7
(Speed setting for output 1, 2, 6 or 7)
Power:
l1, l2
(kW of heat meter 1 or 2)
kWh:
k1, k2
(kWh of heat meter 1 or 2)
MWh:
m1, m2
(MWh of heat meter 1 or 2)
Date: t1
Time: z1
BL-NET CAN network inputs:
The network inputs can be defined using a browser in the "
GSM-Einstellungen
" ("
GSM
settings
") menu of the BL-NET (see the relevant chapter).
Analogue input:
a0…af
(Analogue network inputs 1…16)
Digital input:
d0…df
(Digital network inputs 1…16)
NOTE:
The inputs and outputs are
numbered from zero in hexadecimal
(see hexa-
decimal table)!
This results in (e.g.) the definition "e0" for input 1 and "ef" for input 16.
Hexadecimal table:
dec
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
hex
0 1 2 3 4 5 6 7 8 9 a b c d e f
Example:
$d1ef
… Data line 1, input 16
$d2a0
… Data line 2, output 1
$n1a1
… Network, analogue network input 2