background image

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

8

Operation                               

The SZ1024 and SZ1033 are used when a heat pump 

needs to have its reversing valve operated directly by 

the thermostat. Some heat pumps will require a conven-

tional thermostat, where the heat pump internally con-

trols the position of the reversing valve.

When there is no call for heating or cooling, the revers-

ing valve is in the cooling position. On a call for cooling, 

the fan is cycled on, and then the compressor(s) are 

cycled on. On a call for heating, the fan is cycled on, the 

reversing valve output changes to the heating position, 

and then the compressor(s) are cycled on. If additional 

heating is required, auxiliary heat is then used.

UNOCCUPIED SETBACK

The SZ1024 and SZ1033 operate in either an occupied 

or unoccupied mode. During the occupied mode, the 

occupied heating and cooling setpoints will be main-

tained, and the fan will operate according to its occupied 

setting. During the unoccupied mode, the unoccupied 

heating and cooling setpoints will be maintained, and 

the fan will operate according to its unoccupied setting. 

The occupied LED will be lit when the unit is operating 

in the occupied mode.
The occupied schedule may be set utilizing the internal 

time clock or, with SZ1024 and SZ1033, DI3 may be 

used with an external time clock, whereas when DI3 

is closed, the unit is in the occupied mode. The Smart 

Recovery function is disabled when DI3 is used for 

external time clock.

OVERRIDE

A timed override is available using the button on the 

face of the thermostat or through momentary contacts 

wired into the OVR terminal. The amount of time the unit 

will be overridden is set from 0 to 255 minutes in the 

programming screen. This override behaves differently 

depending on the mode the thermostat is operating in 

(occupied or unoccupied) and the options that have 

been enabled within the software.
In standard mode, the override only activates in unoc-

cupied mode and takes the thermostat into occupied 

mode. If "Override for Occupied Period" is enabled 

using the software, the override also activates in occu-

pied mode and takes the thermostat into unoccupied 

mode. In either case, you are able to view the time 

remaining in the override period both within the software 

and by using the service button to scroll through the sta-

R

Occupied Times Screen.

 Set hours 

and minutes of start and end times 

for up to two occupied periods.

Occupied Times Screen.

 Set hours 

and minutes of start and end times 

for up to two occupied periods.

NOTE: 

No holidays on SZ1024

 

Schedule Announcement Screen.

 

Announces the next screen. 

   

Copy Schedule Screen. 

Indicate 

whether or not to use the same 

schedule that was used for the 

previous day. If the same schedule 

is used, the following screen is not 

displayed.

Occupied Times Screen.

 Set hours 

or minutes of start and end times for 

up to two occupied periods.

Occupied Times Screen.

 Set hours 

or minutes of start and end times for 

up to two occupied periods.

Holiday Announcement Screen.

 

Announces the next screen. (Not 

available on SZ1024.)

Holidays #1 Screen.

 Set holiday 

periods 1 through 12, month, date, 

and duration for the periods that will 

follow the holiday #1 schedule. (Not 

available on SZ1024.)

 

  

Holiday Announcement Screen.

 

Announces the next screen. (Not 

available on SZ1024.)

   

Holidays #2 Screen.

 Set holiday 

periods 1 through 12, month, date, 

and duration for the periods that will 

follow the holiday #2 schedule. (Not 

available on SZ1024.)

A:08:00 TO 12:00

B:13:00 TO 17:00F

5.

override

COPY MON FOR

TUE? 

 

 

 

NO

clock

setup

SET OCCUPIED

TIMES TUESDAY:

clock

setup

A:08:00 TO 12:00

B:13:00 TO 17:00

clock

setup

7.

8.

9.

override

C:00:00 TO 00:00

D:00:00 TO 00:00

6.

override

clock

setup

The following screens are repeated for 

Wednesday, Thursday Friday Saturday, Sunday.  

Sunday, Holiday #1, and Holiday #2. (No 

holidays on SZ1024.)

C:00:00 TO 00:00

D:00:00 TO 00:00

10.

override

clock

setup

MON 

11-19-01

12:00  AM              72F

clock

setup

HOL1 

01-01-01

DURATION=00       DAYS

12.

override

ENTER DATES FOR

HOLIDAY #2: 

clock

setup

13.

clock

setup

ENTER DATES FOR

HOLIDAY #1:   

11.

HOL2 

01-01-01

DURATION=00       DAYS

clock

setup

14.

override

DAYLIGHT

SAVINGS? 

YES

clock

setup

15.

Daylight Savings Screen.

 Choose to 

have automatic daylight savings adjust-

ments to your time. (Not available on  

SZ1024.)

Main Monitoring Screen.

 (Date not 

shown on SZ1024.)

Summary of Contents for SZ1024

Page 1: ...ch is accessible for adjusting its settings Caution Remove power from thermostat prior to mounting Product Manual Description The SZ1024 and SZ1033 are microprocessor based programmable thermostats de...

Page 2: ...r must be used to power the Superstat Several S Series ther mostats may be powered from the same transformer provided that the transformer has sufficient power Superstats require 8W 24 VAC Caution Do...

Page 3: ...ir sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1033 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock the user...

Page 4: ...m setup SET UNOCCUPIED FAN MODE AUTO 11 program setup SET OCCUPIED FAN MODE ON 10 program setup USER ACCESS TO FAN MODE YES 9 program setup SET SYSTEM MODE AUTO 7 program setup USER ACCESS TO SYSTEM M...

Page 5: ...int for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Set...

Page 6: ...y P or add a time factor P I Time Clock Output Screen Choose whether the auxiliary output will be OPEN during occupied periods and closed during unoccupied periods or CLOSED during occupied periods an...

Page 7: ...4 33 SZ1022 31 Compressor 1 Becomes Cool 1 Compressor 2 Becomes Cool 2 Aux Heat 1 Becomes Heat 1 Aux Heat 2 Becomes Heat 2 Emergency Heat Mode does not exist Aux Heat 1 Must be enabled Step 24 for hea...

Page 8: ...bled using the software the override also activates in occu pied mode and takes the thermostat into unoccupied mode In either case you are able to view the time remaining in the override period both w...

Page 9: ...ges will be turned off and will remain off until the discharge air temperature falls 3 below that limit If the LOW LIMIT is reached the fan and cooling stages will be turned off and will remain off un...

Page 10: ...IARY OUTPUT An auxiliary relay output is available to output a signal based on the occupancy status It is commonly used with an economizer minimum position control or to signal an outdoor air damper t...

Page 11: ...e reading Press the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five de...

Page 12: ...the wiring Short terminals R to W1 W2 Y1 Y2 or B O and see if the heating or cooling comes on This is a check for a mechanical relay failure Both Heating and Cooling Are On If this occurs there are t...

Page 13: ...fan O ccupied Heating Cooling Fan Serv ice Program CO OLER W ARM ER Data switch service status system switch program setup clock setup override 11 19 01 Main Monitoring Screen Press the service butto...

Page 14: ...s described in the setup section User s Guide Inside the hinged door of the thermostat is the SuperstatTM User s Guide This guide is designed to assist the installer in explaining to the user how to o...

Reviews: