2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com
3
Setup
Note:
If using remote sensor(s), the calibration
may need to be adjusted. See “Checkout and
Troubleshooting” section.
TEMPERATURE SENSOR SELECTION
The dipswitches in the cover (shown above) must be
set when using remote room, discharge, and/or outdoor
sensors.
NOTE:
Use the following guide to determine the dip-
switch settings for your application.
Using built-in room sensor only.
(This is the default setting.)
Using built-in room sensor with
discharge air sensor only.
Using built-in room sensor with
outdoor air sensor only.*
Using built-in room sensor with
both discharge and outdoor air
sensors.*
Using remote room sensor only.
Using remote room sensor with
discharge air sensor only.
Using remote room sensor with
outdoor air sensor only.*
Using remote room sensor with
both discharge and outdoor air
sensors.*
* (SZ1033 only)
KEYPAD ACCESS
The dipswitches in the thermostat cover (shown above)
must be set in order to lock the user out of the program
and/or to set the clock and schedule. Use the guide
below to set these dipswitches for your application.
User access may also be limited with an access code
set in programming. (The fan and system switches are
enabled or disabled in programming only, and require no
dipswitch placement.)
Keypad access to both programming and
clock setup. (This is the default setting.)
No keypad access to programming or
clock setup.
Keypad access to programming only.
Keypad access to clock setup only.
Once the dipswitches have been set and you have con-
firmed that the sensors are reading correctly (and pro-
gram and clock setup are finished, if locking out access
with dipswitches), secure the cover to the base with the
two set screws located a the top right and the left side.
1 2 3 4 5
REF A B
1 2 3 4 5
R