background image

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

10

the thermostat to fit your equipment to the building load. 

The offset value is the amount away from the setpoint 

a stage will turn off. By assigning a stage a value other 

than zero, you “anticipate” that the residual heat or cool-

ing in the duct or the other stages will bring the tempera-

ture back to setpoint. In most cases, the first stage is set 

to zero. The differential value is the difference between 

the on and off points. This value depends on the load 

and on the equipment size. If the equipment is large for 

the load, you may want to make this value as high as 5 

to prevent equipment cycling. If the equipment is small 

compared to the load, or if tight control is desired, you 

may want to make this value as low as 1. 
The fact that the stages are configurable allows unused 

stages to be set to activate physical alarms if desired. 
In summary, unlike most other multi-stage program-

mable thermostats, the Superstat allows independent 

adjustments of "offsets" and "differentials" for stages of 

heating and cooling.  The offset settings can be viewed 

as setpoints for the second and third stages and are pro-

grammed in the Superstat in the number of degrees (i.e. 

1,2,3…) beyond the heating and cooling setpoints (tem-

peratures to be maintained).  
The differential for each stage can be viewed as the 

"anticipator" function used in mechanical thermostats.

P + I OPTION

The SZ1024 and SZ1033 also have a P+I option. Without 

enabling this option, stages turn on and off based on 

temperature vs. setpoint alone, as described above. By 

enabling this option, you allow a time factor to be added. 

This is useful when you are forced to have a large differ-

ential due to equipment size. At times when the building 

load is low, the temperature could potentially sit a few 

degrees off setpoint for some time. With the time factor 

added, the thermostat would compensate for this, turning 

on the equipment even though the temperature had not 

reached the limits described above. 

DI2 COOL LOCKOUT

DI2 may be set as cool lockout for operation with econo-

mizers. An outdoor temperature switch may be wired in 

such that when DI2 is closed, the second stage of cool-

ing is disabled.  

SMART RECOVERY

“Smart Recovery” may be enabled to insure occupant 

comfort while saving money. It takes the building load 

into consideration and ramps the setpoint when going 

from the unoccupied mode to the occupied mode. At the 

beginning of the occupied mode, the occupied setpoint 

will be reached, many times without the need for the 

second stage to come on. This feature is automatically 

disabled when DI3 is set to external time clock. 

AUXILIARY OUTPUT

An auxiliary relay output is available to output a signal 

based on the occupancy status. It is commonly used with 

an economizer minimum position control, or to signal an 

outdoor air damper to open in occupied times in lieu of an 

economizer. It may also be used for lighting or hot water 

heaters. Keep in mind that although it is an isolated relay 

(separate common terminal), it is rated at 24 VAC. For 

loads that exceed this, use an external relay. It may be 

set to be open (NO) or closed (NC) when the thermostat 

is operating in the occupied mode, and will be the oppo-

site during the unoccupied mode. 

BUILT-IN DELAYS

The SZ1024 and SZ1033 have delays built into the pro-

gramming sequences to protect equipment. The fan has 

a minimum on and off time of 30 seconds. When the fan 

is in AUTO mode, it will come on 30 seconds before the 

heating or cooling stages are allowed to sequence on, 

and remain on for 2 minutes after the heating or cool-

ing stages sequence off. Each stage has a minimum on 

and off time of two minutes. There is a minimum of two 

minutes between when one stage turns on until the next 

stage is allowed to turn on, as well as when one stage 

turns off until the next stage is allowed to turn off.

DELAY ON POWER UP

The SZ1024 and SZ1033 have an adjustable delay on 

power up. When several thermostats are used at one 

location, and the power goes out, most thermostats turn 

all of the units back on at the same time on regain of 

power, creating a demand peak. The thermostat allows 

you to set a value, in seconds, where no outputs are 

allowed to turn on for that length of time on power up. 

Setting each unit to a different delay allows you to soft 

start your system, and thus prevent this peak. 

Note,

 the 

delay on power up also applies to start of occupied time.

DAYLIGHT SAVINGS TIME

Beginning in 2007, Daylight Saving Time (DST) in the 

U.S. will be extended by having an earlier change to DST 

in spring and a delay in switching back to standard time in 

fall. However, this change may only be temporary, as this 

"new" schedule is only in effect for a 2 year trial period. 

After that, the DST schedule may revert back, stay the 

same, or be something completely different. Products 

shipped starting in 2007 with firmware version 1.5 or 

higher accommodate the new DST schedule. Products 

shipped starting in 2008 with firmware version 2.0 or 

higher accommodate the new DST schedule and have 

the ability to be programmed to accommodate any future 

schedules that may be used. Should the schedule change 

and you need to customer program the DST start and end 

dates, simply enable the "Daylight Savings Time" option 

within the software and enter the starting month + week 

and the ending month + week.

R

Heat

Setpoint

Cool

Setpoint

ON

ON

ON

ON

OFF

OFF

OFF

OFF

Differential

Differential

Offset

Offset

Differential

Differential

ON

OFF

ON

OFF

Offset

Differential

Differential

Offset

Summary of Contents for SZ1024

Page 1: ...ch is accessible for adjusting its settings Caution Remove power from thermostat prior to mounting Product Manual Description The SZ1024 and SZ1033 are microprocessor based programmable thermostats de...

Page 2: ...r must be used to power the Superstat Several S Series ther mostats may be powered from the same transformer provided that the transformer has sufficient power Superstats require 8W 24 VAC Caution Do...

Page 3: ...ir sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1033 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock the user...

Page 4: ...m setup SET UNOCCUPIED FAN MODE AUTO 11 program setup SET OCCUPIED FAN MODE ON 10 program setup USER ACCESS TO FAN MODE YES 9 program setup SET SYSTEM MODE AUTO 7 program setup USER ACCESS TO SYSTEM M...

Page 5: ...int for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Set...

Page 6: ...y P or add a time factor P I Time Clock Output Screen Choose whether the auxiliary output will be OPEN during occupied periods and closed during unoccupied periods or CLOSED during occupied periods an...

Page 7: ...4 33 SZ1022 31 Compressor 1 Becomes Cool 1 Compressor 2 Becomes Cool 2 Aux Heat 1 Becomes Heat 1 Aux Heat 2 Becomes Heat 2 Emergency Heat Mode does not exist Aux Heat 1 Must be enabled Step 24 for hea...

Page 8: ...bled using the software the override also activates in occu pied mode and takes the thermostat into unoccupied mode In either case you are able to view the time remaining in the override period both w...

Page 9: ...ges will be turned off and will remain off until the discharge air temperature falls 3 below that limit If the LOW LIMIT is reached the fan and cooling stages will be turned off and will remain off un...

Page 10: ...IARY OUTPUT An auxiliary relay output is available to output a signal based on the occupancy status It is commonly used with an economizer minimum position control or to signal an outdoor air damper t...

Page 11: ...e reading Press the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five de...

Page 12: ...the wiring Short terminals R to W1 W2 Y1 Y2 or B O and see if the heating or cooling comes on This is a check for a mechanical relay failure Both Heating and Cooling Are On If this occurs there are t...

Page 13: ...fan O ccupied Heating Cooling Fan Serv ice Program CO OLER W ARM ER Data switch service status system switch program setup clock setup override 11 19 01 Main Monitoring Screen Press the service butto...

Page 14: ...s described in the setup section User s Guide Inside the hinged door of the thermostat is the SuperstatTM User s Guide This guide is designed to assist the installer in explaining to the user how to o...

Reviews: