9

tus screens. If the occupant desires to return the ther-

mostat to unoccupied or occupied operation (depending 

on how the override was used) before the override time 

remaining elapses, they may press the override button 

again.
Additionally, an "Override Hold" feature is built into the 

thermostats. When in unoccupied mode, pressing the 

override once and then pressing/holding it for 5 seconds 

puts the thermostat into a "hold” mode (the override 

LED on the thermostat will flash quickly to confirm the 

mode change). In this mode, the override setpoints are 

used until the next occupied period is reached or until 

the thermostat is manually taken out of the "hold" mode 

by pressing the override button again. This feature 

also works when the "Override for Occupied Period" is 

enabled BUT starting from the occupied mode and hold-

ing the thermostat in the unoccupied state.

A continuous override is available through the DI3 con-

tact or the software. If DI3 is set to external override, the 

unit will be in the occupied mode whenever the DI3 con-

tact is closed. When using this option, the timed over-

ride may still be activated. 

SETBACK AND OVERRIDE APPLICATIONS

In most applications, it is desired to maintain a regular 

schedule, and allow timed override with the button on 

the face or with a remote momentary contact. 
To allow a regular schedule, and also automatically 

override with the use of an occupancy or light sensor, 

set DI3 to external override and set it up so that the 

contact is closed when you want the override.  
For applications where a room might not be used on a 

regular schedule, such as conference rooms, set DI3 

to external time clock and close the contact when you 

want the room occupied, such as with a switch or wind-

up timer. If each occupancy period is about the same, 

(theaters, meetings) another option is to set the DI3 to 

external time clock, and use the timed override button to 

put the unit in occupied mode. 
To make the unit always occupied, set DI3 to external 

time clock and short the DI3 terminal to ground. 

DISCHARGE AIR TEMPERATURE SENSING

The SZ1024 and SZ1033 accept a remote discharge air 

sensor  for monitoring purposes.  (See setup instruc-

tions for dipswitch placement for this option.) 
Choose YES in programming screen #32 only if you are 

using a discharge air sensor and you want to enable the 

discharge air temperature high and low limit functions. If 

NO is chosen, the discharge air will still be monitored. 
When the function is enabled, a HIGH LIMIT and LOW 

LIMIT are entered in steps #33 and #34. If the HIGH 

LIMIT is reached, the fan and heating stages will be 

turned off and will remain off until the discharge air 

temperature falls 3° below that limit. If the LOW LIMIT 

is reached, the fan and cooling stages will be turned off 

and will remain off until the discharge air rises 3° above 

that limit. When either limit is reached, the service LED 

will be on until normal operation resumes.     
The discharge air span is 0°F to 150°F (-17.8°C to 

65.6°C).

OUTDOOR AIR TEMPERATURE SENSING

The SZ1033 accepts a remote outdoor temperature sen-

sor for monitoring purposes. (See setup instructions for 

dipswitch placement for this option.) 
Choose YES in programming screen #35 only if you are 

using an outdoor air sensor and you want to enable the 

outdoor air heating and cooling lockout functions. If NO 

is chosen, the outdoor air will still be monitored. 
When the function is enabled, a COOLING LOCKOUT 

TEMP and HEATING LOCKOUT TEMP are entered 

in steps #36 and #37. If the outdoor temperature falls 

below the COOLING LOCKOUT TEMP, all cooling 

stages will be locked out and will remain locked out until 

the outdoor air temperature rises 2° above the lockout 

temperature. If the outdoor temperature rises above the 

HEATING LOCKOUT TEMP, all heating stages will be 

locked out and will remain locked out until the outdoor 

air temperature falls 2° below the lockout temperature. 
The outdoor air span is -40°F to 160°F (-40.0°C to 

71.1°C). This is the outdoor air heat feature and emer-

gency heat feature.

FAN PROVING

The SZ1024 and SZ1033 allow DI1 to be set for fan 

proving to protect equipment on fan failure. To utilize 

this function, input a pressure or current switch which 

tells when the fan is running. If the thermostat closes its 

fan contact, and the DI1 is not closed after thirty sec-

onds, the system will go to OFF, disabling all outputs, 

the fan LED will turn off, and the service LED will be lit 

until the system is manually reset by switching the sys-

tem to a mode other than OFF.  

DI2 SETPOINT SHIFT

The SZ1024 and SZ1033 allow DI2 to be set for set-

point shift for energy demand setback. This is enabled 

by setting DI2 to the MONITOR mode. A digital contact 

that closes when setback is needed should be wired into 

DI2. You may specify a number of degrees such that, 

when the thermostat is operating in the occupied mode, 

and DI2 is closed, the heating setpoint will be lowered 

this number of degrees, and the cooling setpoint will 

be raised this number of degrees. The fan will continue 

to operate according to its occupied setting. If you are 

using DI2 as monitor for another purpose, make sure to 

set this value to zero.

 

     

 
STAGE OUTPUT PARAMETERS

The SZ1024 and SZ1033 will control up to two stages 

each of compression, and up to two stages of auxiliary 

heat. It is recommended that all unused stages be dis-

abled. 
For each stage, you may specify an offset and a differ-

ential value. This allows you to adjust the operation of 

R

Summary of Contents for SZ1024

Page 1: ...ch is accessible for adjusting its settings Caution Remove power from thermostat prior to mounting Product Manual Description The SZ1024 and SZ1033 are microprocessor based programmable thermostats de...

Page 2: ...r must be used to power the Superstat Several S Series ther mostats may be powered from the same transformer provided that the transformer has sufficient power Superstats require 8W 24 VAC Caution Do...

Page 3: ...ir sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1033 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock the user...

Page 4: ...m setup SET UNOCCUPIED FAN MODE AUTO 11 program setup SET OCCUPIED FAN MODE ON 10 program setup USER ACCESS TO FAN MODE YES 9 program setup SET SYSTEM MODE AUTO 7 program setup USER ACCESS TO SYSTEM M...

Page 5: ...int for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Set...

Page 6: ...y P or add a time factor P I Time Clock Output Screen Choose whether the auxiliary output will be OPEN during occupied periods and closed during unoccupied periods or CLOSED during occupied periods an...

Page 7: ...4 33 SZ1022 31 Compressor 1 Becomes Cool 1 Compressor 2 Becomes Cool 2 Aux Heat 1 Becomes Heat 1 Aux Heat 2 Becomes Heat 2 Emergency Heat Mode does not exist Aux Heat 1 Must be enabled Step 24 for hea...

Page 8: ...bled using the software the override also activates in occu pied mode and takes the thermostat into unoccupied mode In either case you are able to view the time remaining in the override period both w...

Page 9: ...ges will be turned off and will remain off until the discharge air temperature falls 3 below that limit If the LOW LIMIT is reached the fan and cooling stages will be turned off and will remain off un...

Page 10: ...IARY OUTPUT An auxiliary relay output is available to output a signal based on the occupancy status It is commonly used with an economizer minimum position control or to signal an outdoor air damper t...

Page 11: ...e reading Press the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five de...

Page 12: ...the wiring Short terminals R to W1 W2 Y1 Y2 or B O and see if the heating or cooling comes on This is a check for a mechanical relay failure Both Heating and Cooling Are On If this occurs there are t...

Page 13: ...fan O ccupied Heating Cooling Fan Serv ice Program CO OLER W ARM ER Data switch service status system switch program setup clock setup override 11 19 01 Main Monitoring Screen Press the service butto...

Page 14: ...s described in the setup section User s Guide Inside the hinged door of the thermostat is the SuperstatTM User s Guide This guide is designed to assist the installer in explaining to the user how to o...