background image

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

12

7. Press the cooler (down) button until the heating set-

point is one degree less than the current tempera-

ture. The reversing valve, compressors, and heating 

stage(s) will sequence off. The fan will turn off 2 min-

utes after the reversing valve. 

8. Press the cooler button until the cooling setpoint is 

less than the current temperature by at least five 

degrees. The fan will come on. The compressors(s) 

will sequence on after 30 seconds. 

9. Press the warmer button until the cooling setpoint is 

greater than the current temperature by one degree. 

The compressor(s) will sequence off. The fan will turn 

off 2 minutes after the last compressor.

10. Go back to programming step #15 and set the set-

point adjust limit back to the desired value. Make any 

other changes in programming, clock, and schedule. 

Set the fan and system modes to their desired set-

tings. 

11. If using remote sensor(s), verify that the reading is 

correct.  If not, see 

Wrong Temperature Display

 in 

Troubleshooting

 section.

TROUBLESHOOTING
No Display

Check for 24 VAC on terminals “+24” and “-24”. Check 

the cable connecting the cover to the base for a good 

connection.

Fan Does Not Come On

The fan is on whenever the fan LED is on. If the fan 

should be on, but the fan LED is off, check the fan and 

system switch modes, and the unoccupied fan mode 

in programming. If the fan is off but the fan LED is on, 

check wiring. Short terminals “R” to “G” and see if the 

fan comes on. This is a check for a mechanical relay 

failure.

Heating or Cooling Does Not Come On 

 

At least one stage of heating is on whenever the heat-

ing LED is on, and at least one stage of cooling is on 

whenever the cooling LED is on. If heating or cooling 

should be on but the heating or cooling LED is off, 

check the fan and system switch modes. Also, check 

the heating and cooling setpoints, offsets and differen-

tials, and the room temperature to be sure heating or 

cooling should be on. If using outdoor air heating and 

cooling lockouts, or discharge air high and low limits, 

check their values to be sure heating or cooling is 

allowed. If heating or cooling is off, but the correspond-

ing LED is on, check the wiring. Short terminals “R” to 

“W1”, “W2”, “Y1”, “Y2”, or “B/O” and see if the heating 

or cooling comes on. This is a check for a mechanical 

relay failure. 

Both Heating and Cooling Are On

If this occurs, there are two possibilities. Either the 

reversing valve operation is set incorrectly, or the heat 

pump requires a conventional thermostat for proper 

operation. (See programming through the Key Pad, 

Step 5).

Wrong Temperature Display

Initially, verify the wiring connections to check for 

problems (poor connections, opens, or shorts). If the 

temperature is at a minimum or maximum reading, 

check that the sensor dipswitch positions are correct as 

shown in the Setup section of this document. Also, ver-

ify the resistance reading for the sensor in question. A 

remote sensor should read 1080 to 1090 ohms at room 

temperature. The built-in sensor should read 108 to 109 

ohms at room temperature. If any of the temperatures 

are still reading slightly high or low, you can add in a 

temperature offset (calibration) using Ubiquity or TCS 

Insight. In Ubiquity, you can edit the calibration offset 

for each temperature input (room, discharge, outdoor 

air, etc.) on the controller's programming page. For 

example, if the room temperature is reading 2 degrees 

high, you would subtract 2 from the existing offset in 

the room temperature calibration offset field and submit 

the page. In TCS Insight, the process is similar. Refer 

to the Calibrate Using TCS Insight Tech Bulletin # 1019 

for details. As a last resort and only when directed to do 

so by TCS technical support, you may be able to use 

the on-board adjustment pots. Refer to the Thermostat 

Sensor Calibration Tech Bulletin # 1005 for details.

Service LED is On

If the service LED is on, it may be for monitoring pur-

poses or it may indicate a critical problem. The first 

monitoring screen accessed by pressing the service sta-

tus button will display why the light is on.

Outputs Will Not Shut Off

First check the room temperature and the setpoints and 

determine whether the output should be on. There are 

delays and minimum on and off times for the fan and 

heating and cooling stages. Also, check the service 

status menus to verify that the outputs are on. Turning 

the system to “off” will instantly turn all outputs off. The 

thermostat can be reset by pressing the system switch 

button and the service status button simultaneously.  

R

T1

T2
T3

1  2

1  2  3  4  5

adjust display contrast

Summary of Contents for SZ1024

Page 1: ...ch is accessible for adjusting its settings Caution Remove power from thermostat prior to mounting Product Manual Description The SZ1024 and SZ1033 are microprocessor based programmable thermostats de...

Page 2: ...r must be used to power the Superstat Several S Series ther mostats may be powered from the same transformer provided that the transformer has sufficient power Superstats require 8W 24 VAC Caution Do...

Page 3: ...ir sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1033 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock the user...

Page 4: ...m setup SET UNOCCUPIED FAN MODE AUTO 11 program setup SET OCCUPIED FAN MODE ON 10 program setup USER ACCESS TO FAN MODE YES 9 program setup SET SYSTEM MODE AUTO 7 program setup USER ACCESS TO SYSTEM M...

Page 5: ...int for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Set...

Page 6: ...y P or add a time factor P I Time Clock Output Screen Choose whether the auxiliary output will be OPEN during occupied periods and closed during unoccupied periods or CLOSED during occupied periods an...

Page 7: ...4 33 SZ1022 31 Compressor 1 Becomes Cool 1 Compressor 2 Becomes Cool 2 Aux Heat 1 Becomes Heat 1 Aux Heat 2 Becomes Heat 2 Emergency Heat Mode does not exist Aux Heat 1 Must be enabled Step 24 for hea...

Page 8: ...bled using the software the override also activates in occu pied mode and takes the thermostat into unoccupied mode In either case you are able to view the time remaining in the override period both w...

Page 9: ...ges will be turned off and will remain off until the discharge air temperature falls 3 below that limit If the LOW LIMIT is reached the fan and cooling stages will be turned off and will remain off un...

Page 10: ...IARY OUTPUT An auxiliary relay output is available to output a signal based on the occupancy status It is commonly used with an economizer minimum position control or to signal an outdoor air damper t...

Page 11: ...e reading Press the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five de...

Page 12: ...the wiring Short terminals R to W1 W2 Y1 Y2 or B O and see if the heating or cooling comes on This is a check for a mechanical relay failure Both Heating and Cooling Are On If this occurs there are t...

Page 13: ...fan O ccupied Heating Cooling Fan Serv ice Program CO OLER W ARM ER Data switch service status system switch program setup clock setup override 11 19 01 Main Monitoring Screen Press the service butto...

Page 14: ...s described in the setup section User s Guide Inside the hinged door of the thermostat is the SuperstatTM User s Guide This guide is designed to assist the installer in explaining to the user how to o...

Reviews: