11.1 Technical Data
11.1.1 Electrical Part
Input data (DC side)
Parameter description
Reference value
Maximum DC voltage (Vdc)
600
PV grounding mode
PV-grounding (ANSI requirements)
MPPT voltage range of DC input (V)
DC320 ~ DC580 (full load)
Maximum PV array input power (kW)
550
Maximum input current (A)
1600
Maximum input short circuit current (A)
2500
Maximum input source backfeed current to
input source
3180 A peak/ 85.33 ms
Output data (grid side)
Parameter description
Reference value
Rated output power(kW)
500
Normal output voltage(Vac)
200(defalt setting value)
Allowable grid voltage range (three-phase)
-12% ~ +10 %, i.e. 176Vac ~ 220Vac
Normal output frequency(Hz)
60(defalt setting value)
Operating frequency(Hz)
59.8(this operating point is
adjustable) ~60.5
Maximum continuous output current (A)
1443(ac)
Maximum output fault current (A) / duration (ms)
1270 rms/997, 6600 peak/ 997
Maximum output overcurrent protection (A)
2000 (internal circuit breaker)
Maximum continuous output power(kW)
500
Synchronization in-rush current
Type 2/ 26.4 A rms, 65.0 A peak, 19.3
ms