TC500K3US-O Installation Instructions
67
When other connecting schemes are selected, please contact with
TBEA professionals. If the customer selects other connecting schemes
arbitrarily, and thus influence the product installation and application,
TBEA shall not assume any responsibility.
Steps of DC side wiring are as follows:
Step 1
Disconnect the DC side of the power distribution inverter to ensure
the DC side wiring is not charged.
Step 2
Measured with a multimeter to ensure that the open circuit voltage
of the PV array does not exceed 600Vdc.
Step 3
Use a multimeter to confirm the positive and negative.
Step 4
Strip the insulation of the cable end 5mm longer as the wiring hole.
The DC input terminal of the TC500K3US-O is connected only 1 copper cable
to each of the positive and negative corresponding to the DT wiring terminal of
which the diameter shall be greater than 11mm.
Step 5
Wire the DT - wiring terminal.
(1)
Insert the bare copper wire into the wring hole.