![TBEA TC500K3US-O Installation Manual Download Page 19](http://html1.mh-extra.com/html/tbea/tc500k3us-o/tc500k3us-o_installation-manual_823554019.webp)
TC500K3US-O Installation Instructions
13
2.2.4 Notes on Shutdown
There are two cases for shutdown, in normal maintenance and in fault
occurring. The procedures for respective shutdown are as follows:
Normal maintenance and overhaul
Shutdown procedure:
(1)
Turn the key switch to “
OFF
”.
(2)
Observe the LCD display until the rate of work of the display is
shown as “
0
”.
(3)
Turn both AC and DC circuit breakers to “
OFF
”.
(4)
Disconnect the front and rear breakers of the inverter.
When fault or emergency occurring
Shutdown procedure:
(1)
Press down the emergency stop button then turn the key switch to
“
OFF
”.
(2)
Turn both AC and DC circuit breakers to “
OFF
”, and then
disconnect the preamplifier breaker and after stage amplifier circuit
breaker.
(3)
Turn the key switch to “
OFF
”.