Energier pro User Manual
30
For the user operation safety, cut off the power before installation.
We recommend connecting a DC fuse corresponding to the conductor between battery and Energier pro bi-directional inverter,
which will offer protection to the battery cable. Please refer to following chart of our recommendations.
Ensure that the Energier pro bi-directional inverter has the correct DC voltage with your existing battery system.
Install Energier pro bi-directional inverter as close to the batteries as possible reducing the voltage drop on cable for the better
performance of the equipment.
On the AC output side, we recommend connecting the output from Energier pro bi-directional inverter to a suitable Residual
Current Circuit Breaker and Circuit Breaker.
The neutral of this equipment is not connected to the earth. If requested, additional devices need to be installed internally.
Please contact your installer.
Do not connect the output of this equipment to your AC system at the same time as any other AC source
such as the 230V external mains or a generator.
6. Installation and Connection
6.1 General advice
12 VDC model
Systemcapacity
24 VDC model
48 VDC model
CF20xx
CF30xx
CF40xx
500 A
CF50xx
CF60xx
CF80xx
/
/
175 A
/
/
/
400 A
/
/
200 A
250 A
300 A
CF12xx
CF08xx
CF16xx
250 A
300 A
150 A
200 A
100 A
150 A
250 A
75 A
125 A
125 A
/
/
80 A
/
Summary of Contents for Energier Pro Series
Page 1: ...User Manual Energier Pro series Bi directional inverter TBB Power CO ltd www tbbpower com A3 1...
Page 22: ...Energier pro User Manual 16 3 1 2 RCF remote 3 1 3 Vision Lite 3 1 4 AGS 3 1 5 TAI...
Page 25: ...Energier pro User Manual 19 3 2 4 AGS 3 2 5 TAI...
Page 39: ...Energier pro User Manual 33 CF 2000 VA 4000 VA Model CF 5000 VA 8000 VA Model...