Energier pro User Manual
26
Using DIP Switch 1, you can set the system in weak grid mode. Please refer to chapter 2.9 for explanation.
The default setting was OFF, 10.5 VDC (12 V model) / 21VDC (24 V model) / 42 VDC (48 V model).
Through DIP Switch 2, you could configure the system in solar mode. For explanation, please refer to chapter 2.10.
4.2 Weak Grid mode
4.3 SOLAR mode
Through the DIP Switch 3, you can configure the premium low voltage protection level for your system. Following please find
following the data.
The following DOD is ONLY estimation. The exact measure of the battery SOC is almost impossible with only electrical parameter.
It may vary according to discharge current, battery healthy etc.
4.4 Low Voltage disconnect (LVD)
Please refer to following chart for all setting of DIP Switch:
DIP Switch
1
2
3
Weak Grid Mode Solar Mode
LVD
6
5
EQ
7
P.S.
8
GEN Mode
4
Battery Type
This configuration will adjust the minimum voltage of AC input which Energier pro bi-directional inverter will qualify
and pass through to your AC appliance. Majority of present appliance will work properly. However, before perform
this configuration, please double check the electrical rating of connected load. Low voltage might cause damage for
particular load.
DS3
12 VDC model
24 VDC model
48 VDC model
off
on
11.7 VDC
23.4 VDC
46.8 VDC
ab. 60%
solar or backup
10.5 VDC
21.0 VDC
42.0 VDC
est DOD
>90%
recommendation
mobile
Summary of Contents for Energier Pro Series
Page 1: ...User Manual Energier Pro series Bi directional inverter TBB Power CO ltd www tbbpower com A3 1...
Page 22: ...Energier pro User Manual 16 3 1 2 RCF remote 3 1 3 Vision Lite 3 1 4 AGS 3 1 5 TAI...
Page 25: ...Energier pro User Manual 19 3 2 4 AGS 3 2 5 TAI...
Page 39: ...Energier pro User Manual 33 CF 2000 VA 4000 VA Model CF 5000 VA 8000 VA Model...