Energier pro User Manual
36
6.4 Install the temperature sensor
6.5 Install the voltage sensor
Pull through the TS cable through gland and connect it on socket marked “BTS Interface”.
Please glue the temperature sensor, which was plugged into BTS socket at central panel, on the SIDE of battery and secure
the attachment.
Please notice the cable supplied is around 300cm. Do not pull cable too hard avoid loose contact loose.
Pull through the VS cable through gland and connect it on port marked “Voltage Sensor”. Please refer to following fig.
The minus (-) of voltage sensor should be connected to the minus (-) of service battery, and the positive (+) of voltage sensor
should be connected to the positive (+) of service battery. Wrong connection will damage the Energier pro bi-directional inverter.
Please secure the sensor on battery terminal.