Energier pro User Manual
49
9.3.3 No charging delivered
Reason 1
:
AC input wire loose connection.
Solution : Secure the connection.
Reason 2
:
Wrong connection of N and PE of AC input.
Solution : Correct the connection.
Reason 3
:
Check if using Generator as AC input.
Solution : Change working mode to GEN Mode through dip switch 8 at POWER PCB.
9.3.4 Normal mode and Power save mode keep changing over
Reason 1
:
Energier pro bi-directional inverter work in power save mode but the load was fluctuating .
Solution : Change work mode to normal mode.
9.3.5 Normal mode or Charger Only mode not working
Reason 1
:
The work mode setting on Energier pro bi-directional inverter and on RCF was different with each other.
Solution : Put main switch at Energier pro bi-directional inverter at OFF, using RCF to set the working mode.
Phenomenon 5
:
No output,fault and overtemp lights illuminate.
Reason
:
Over temperature shutdown.
Solution
:
Check if there is good ventilation on installation site; check if fan was blocked.
Phenomenon 6
:
No output, long beep, fault light illuminate.
Reason
:
Fan failure/block.
Solution
:
Check if fan is blocked; check fan wire connection well.