Basic Operations
------------------------------------------------------------------------------------
35
Fan Alarm
※This function is only 400LN/LAN
It monitors the rotation status of the cooling fan motor of the power supply.
When detecting an alarm, you can set whether to continue or stop the output of the power supply.
Setting/Canceling Fan Alarm
Setting for Fan Alarm Detection
Press the Function FUNC key.
「FUNC.」Lamp lights.
The Setting Item Number will display on the top Number Display
And the parameter will be displayed in the bottom Number Display.
Select Item No.14 with the VOLTAGE dial.
Set parameter to 0 or 1 with the CURRENT dial.
Parameter=0 When fan alarm is detected, output continues.
Parameter=1 When fan alarm is detected, output stops.
Press the FUNC key to finalize settings.
OUTPUT
PRESET
OVP
OCP
FUNC.
ALARM RESET
CC
CV
OUTPUT POWER (%)
STEP
CURRENT
STEP
VOLTAGE
PRESET FUNC. REMOTE LOCK
20
60
100 LMT
40
80
CC
CV
OUTPUT POWER (%)
STEP
CURRENT
STEP
VOLTAGE
PRESET FUNC. REMOTE LOCK
20
60
100 LMT
40
80
OUTPUT
PRESET
OVP
OCP
FUNC.
ALARM RESET
If you countinue to use the fan while it is stopped, the over heating
protection circuit operates and output may stop.
Caution
Summary of Contents for ZX-S-LN Series
Page 1: ...Constant Voltage Constant Current DC Power Supply series Instruction Manual...
Page 13: ...About this Product 10 This is blank page...
Page 63: ...Useful Function 60 This is blank page...
Page 151: ...Controlling with External Analog Contact Signals 148 This is blank page...
Page 157: ...Special Loads 154 This is blank page...
Page 199: ...Specifications 196 This is blank page...
Page 200: ...197 External Diagrams ZX S 400LN 400LAN 4 M3...
Page 201: ...Appendix 198 ZX S 800LN 800LAN...
Page 202: ...Appendix 199 ZX S 1600LN 1600LAN...