Chapter 2 TL1 Reference
Retrieve All Alarms
42
SSU-2000e Technical Reference
12713140-003-2 Revision E.01 – January 2007
Retrieve All Alarms
This command reports all active alarms from the SSU-2000e or designated modules
or ports with an aid indicating which module or port is generating the alarm. The
response is the complied message followed by the alarm report message(s).
There may be no lines or there may be multiple lines in the report, one for each
active alarm. There is no report message for modules or ports that have no alarm
condition.
Syntax
RTRV-ALARM:[tid]:[aid]:ctag;
or
RTRV-ALM:[tid]:[aid]:ctag;
Response Format
<cr><lf><lf>
sid date time<cr><lf>
M
ctag COMPLD<cr><lf>
"<aid>,aidtype:ntfcncde,condtype,srveff,\"condscr\"<cr><lf>
"<aid>,aidtype:ntfcncde,condtype,srveff,\"condscr\"<cr><lf>
.
.
"<aid>,aidtype:ntfcncde,condtype,srveff,\"condscr\"<cr><lf>
;
where:
aid
= module or port access identifier
ntfcncde
= notification code (CR, MJ, MN, CL)
condtype
= condition type (event number)
srveff
= service affecting flag (SA, NSA)
condstr
= condition description string
Related Commands
Parameter
Value
Description
[aid]
ALL
Retrieves information for all alarms that are currently
active in the entire shelf.
SxAy[-z]
Retrieves information for all alarms that are currently
active in the specified module [or port].