Chapter 2 TL1 Reference
Set Signal Fault Alarm Parameters
150
SSU-2000e Technical Reference
12713140-003-2 Revision E.01 – January 2007
Set Signal Fault Alarm Parameters
These commands set the input error and clear parameters for signal faults on the
specified DS1, E1, or CC Input module or port.
Syntax
SET-PRMTR-AIS:tid:[aid]:ctag::[errcnt],[clrcnt];
SET-PRMTR-BPV:tid:[aid]:ctag::[errcnt],[clrcnt];
SET-PRMTR-CRC:tid:[aid]:ctag::[errcnt],[clrcnt];
SET-PRMTR-LOS:tid:[aid]:ctag::[errcnt],[clrcnt];
SET-PRMTR-OOF:tid:[aid]:ctag::[errcnt],[clrcnt];
Related Commands
Retrieve Signal Fault Alarm Parameters
Parameter
Format
Description
aid
SxAy[-z]
Sets the alarm level for the specfied Input module [or
port].
1
Note:
1
For CC input modules and ports, only the LOS and BPV commands apply; AIS,
CRC, and OOF commands are denied.
errcnt
0-100: LOS
and AIS
0-10000:
OOF, BPV,
and CRC
Specifies the start delay time, which is the number of
seconds that the alarm must be present before the alarm
message is issued.
clrcnt
0-100: LOS
and AIS
0-10000:
OOF, BPV,
and CRC
Specifies the clear delay time, which is the number of
error-free seconds after the alarm condition is cleared
before the alarm indication is cleared.