Parameter setting
Page 39/55
SYCLOPE TERE’O Touch XL
®
Installation, starting, and programming instructions
g)
Communications
Pressing the « Communication » button opens the programming window.
MODBUS section (Local communication RS485 port)
Change MODBUS speed:
Use the buttons on either side of the selection area to scroll through the different
speeds in one direction or the other (300, 1200, 2400, 4800, 9600, 19200, 38400, 57600,
115200).
Change MODBUS parity:
Use the buttons on either side of the selection box to scroll through the different
parities in one direction or the other (None, Even, Odd).
Stop bit(s) information:
This part is not modifiable and is automatically configured according to the choice of
parity that is made.
-
2 for a communication without parity.
-
1 for communication with even or odd parity.
Change MODBUS address:
Press the button to open the numeric keypad and enter the new address.
Communications
MODBUS
Speed
MODEM
Type
Parity
Stop bit(s)
Address
APN SIM card GSM module
19200
None
2
1
No
Mysyclope detting
IP setting
WIFI setting