5.2.1.40
Control Parameters:
if Parameters = pH
5.2.1.40.18
Setpoint
Range: 0.00–14 pH
5.2.1.40.28
P-Band:
Range: 0.00–14 pH
5.2.1.40
Control Parameters:
if Parameters = Ammonia
5.2.1.40.19
Setpoint
Range: 0.00–500 ppm
5.2.1.40.29
P-Band:
Range: 0.00–500 ppm
5.2.1.40.3
Reset time:
The reset time is the time till the step response of a sin-
gle I-controller will reach the same value as it will be suddenly
reached by a P-controller.
Range: 0–9’000 sec
5.2.1.40.4
Derivative time:
The derivative time is the time till the ramp re-
sponse of a single P-controller will reach the same value as it will
be suddenly reached by a D-controller.
Range: 0–9’000 sec
5.2.1.40.5
Control timeout:
If a controller action (dosing intensity) is constantly
over 90% during a defined period of time and the process value
does not come closer to the setpoint, the dosing process will be
stopped for safety reasons.
Range: 0–720 min