7.0 SG-DRL5/DRL5E/DRL5-2L PSTN Line Cards
- 119 -
SG-DRL5 Options 189/289 to 190/290: Handshake and Kiss-off Duration
Default (00)
Some control panels may require a different handshake duration. Each unit has increments of 100 ms, from 100 ms to a maximum of 8.1 seconds. Pro-
gram Options 189/289 to 90 for the desired duration.
00
1 second
04
100 ms
02
200 ms
03
300 ms
04
400 ms
0A
1 second
0C
1.2 second.... and so on
Sur-Gard does not recommend programmed durations longer than 1.5 seconds, as it may not be tolerated by the alarm panel. For special applications, it
may be necessary, but any durations higher than 8.1 seconds are not accurate and may not match the duration programmed.
NOTE: These options only affect steady tones handshakes.
Option 189/289: Handshake #1 duration
Option 18A/28A: Handshake #2 duration
Option 18B/28B: Handshake #3 duration
Option 18C/28C: Handshake #4 duration
Option 18D/28D: Handshake #5 duration
Option 18E/28E: Handshake #6 duration
Option 18F/28F: Handshake #7 duration
Option 190/290: Handshake #8 duration
SG-DRL5 Option 191/291: Inter-Handshake Duration
Default (00)
The line card usually waits for signals from the control panels for four seconds before sending the next handshake, if there are no signals received. In
certain applications, control panels cannot wait long enough to get their own handshake especially if the handshake is programmed as the fifth or later
handshake.
The maximum time allowed for this section is 09 (9 seconds). Program Option 191/291 with one of the following:
00 4-second interval
02 2-second interval
01 1-second interval
03 3-second interval
SG-DRL5 Option 192/292: Pulse Mode
Default (00)
00
=
Standard Pulse Detection
01
=
50 Baud Pulse Detection
02
=
Forced (AAA) Pulse Detection, meaning only PULSE is detected.
8x
=
When this bit is on, it acts as a minimum burst rejection option where x can be
1 to F(1ms to 15 ms) burst duration to reject.
SG-DRL5 Option 193/293: Min Audio Tone
Default (00)
This option is used for 2-way audio tone detection from specific audio panels. This option should be left as default unless otherwise instructed by Sur-
Gard Technical Support.
SG-DRL43-2L Option 194/294: Account Digit Stripping
Default (00)
When Option 194/294 is set to 00 it is disabled.