9 Troubleshooting and Maintenance
55
Fault
Code
Description
Troubleshooting
011
The DC component of
AC current exceeds
inverter limit.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
012
A failure current is
detected.
1. Check the PV strings for ground fault.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
013
Grid
abnormal
is
detected
1. Wait a moment for grid recovery.
2. If the grid parameters exceed the
permissible range, ask utility grid company for
solution.
3. If the grid frequency is within the
permissible range, contact Sungrow Service
Dept..
014
The average grid voltage
exceeds the permissible
range for over 10
minutes.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
015
Grid impedance exceeds
inverter’s limit
1. Check the model of the AC cables.
2. Wait a moment for inverter recovery.
3. If the fault occurs repeatedly, contact
Sungrow Service Dept..
016
The AC output
overloads.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
017
Unbalance between the
three phase voltages is
detected
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
019
The transient bus
voltage is high.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
020
The bus voltage is high.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..
021
PV1 or PV3 input
overcurrent is detected
Check the layout and the wiring of PV1 or PV3
input.
022
PV2 input
overcurrent is detected
Check the layout and the wiring of PV2 input.
023
PV configuration mode
has changed during
inverter running.
Check the PV input configuration mode and
restart the inverter when necessary.
024
Deviation from neutral
point voltage is
detected.
1. Inverter will recover if the deviation value
falls below the protection limit.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept..