User Manual
48
Step 4
Press
to choose country(region) code.
Confirm the settings by
Pressing
ENTER
.
Countries
GB
DE
FR
IT
ES
BE
NL
AT
DK
PT
AU
GR
CN
CZ
KR
SE
RO
TH
TK
US
other
IND
ZAF
CHL
BRA
TPE
Step 5
Select the country(region) code according to
the inverter’s installation country(region). Each
country(region)
code represents
corresponding local protective parameters
that have been preset before delivery. Before
country(region) setting, there is warning
screen.
Warning!
Only qualified personnel rare allowed to
adjust following parameters. Improper
settings may cause damage to the
inverter!
Refer to “10.11 Protection Parameter Setting” for country(region) code explanation. If
the inverter is installed where the country(region) code is not included, please
choose item “Other” and manually set the protective parameters.
If the country(region) code is not set correctly during commissioning, reset
the protective parameters as dictated in “10.11 Protection Parameter
Setting”. There may be faults if otherwise.
Step 6
If the country(region) code set as GR,
a Grid codes page as shown in the
right will appear.
Press
to select
grid code and press ENTER to
confirm.
Grid codes
GR_L
GR_IS
GR
After setting the Country(region) parameter, please proceed to set
other parameters of the inverter in accordance with the specific
requirements of the local grid. Before commissioning, please check
thoroughly if the set parameters meet the local grid requirement.