Description Of Communication Protocol 217
V260 Series High Performance Closed-Loop Vector Inverter User manual
11.1.7 DETAILED MODBUS ADDRESS-FINDING DISTRIBUTION
1) Coil Address Summary (0x1000-0x1100)
Relevant Modbus functional codes: 0x01 (read coil status), 0x05 (write to a single coil), 0x0F (write to
multiple coils)
Register name
Function Description
Access Address
Controlling Digit – Digit 0
Keep
0x1000
Controlling Digit – Digit 1
Operation Allowed
0: Operation banned 1: Operation allowed
0x1001
Controlling Digit – Digit 2
Starting allowed
0: Starting banned 1: Starting allowed
0x1002
Controlling Digit – Digit 3
Keep
0x1003
Controlling Digit – Digit 4
Operation instruction
0: Stop 1:Operation
0x1004
Controlling Digit – Digit 5
Operation direction
0: Positive 1: Negative
0x1005
Controlling Digit – Digit 6
Emergency Stop
0: Invalid 1: Valid
0x1006
Controlling Digit – Digit 7
Free slide stop 0: Invalid 1: Valid
0x1007
Controlling Digit – Digit 8
Keep
0x1008
Controlling Digit – Digit 9
Keep
0x1009
Controlling Digit – Digit 10
Keep
0x100A
Controlling Digit – Digit 11
Keep
0x100B
Controlling Digit – Digit 12
Acceleration/deceleration banned
0: Allowed 1: Banned
0x100C
Controlling Digit – Digit 13
Zero-clearing for integrator input
0: Invalid 1: Valid
0x100D
Controlling Digit – Digit 14
Remote Control
0: Invalid 1: Valid
0x100E
Controlling Digit – Digit 15
Failure Reset 0- >1 Reset
0x100F
DO1
Multi-purpose output terminal 1
0x1020
DO2
Multi-purpose output terminal 2
0x1021
EDO1
Multi-purpose output terminal 3 (extendable card)
0x1030
RO1
Multi-purpose relay output 1
0x1040
ERO1
Multi-purpose relay output 2 (extendable card)
0x1050
Keep
0x1051~
0x1099