144 Description Of Specific Functions
V260 Series High Performance Closed-Loop Vector Inverter User Manual
As frequency output terminal, frequency range of signal output by D03/ Fout: 0.07-100.0KHz.
64~71: Please refer to chapter six
“
chart2
:
Variable table of multi-function output terminal
(
DO/EDO/SDO
)
”
F3.1.15~F3.1.20 DO1~DO3
delay time for switching signal
output ON and OFF
Setting range: 0.01~10.00Sec.
Factory default: 0.0
F3.1.23~F3.1.26 RO1/RO2 delay
time for switching ON/OFF
Setting range: 0.01~10.00Sec.
Factory default: 0.0
This group of parameters are used to define multi-function output terminal DO1~DO3 and time delay of
change for signal state output by multi-function relay RO1/RO2. When signal output by multi-function
terminal and pulled in by relay is effective, terminal will output indicator signal, and relay will pull
in(connection of TA and TC) after delay time set by parameters F3.1.15~F3.1.20, F3.1.23~F3.1.26.
F3.1.27~F3.1.29 Input variables of
monitor 1~3
Setting range: 0~44
Factory default: 0~2
Different state parameters can be monitored by setting the values of F3.1.27~F3.1.29.
F3.1.30~F3.1.35 Upper and lower
limit of monitor 1~3 variables
Setting range: 0.0~100.0%
Factory default:
0.0/100.0
This group of parameters restricts the range of monitoring parameter variables, of which the set values are
relative to the percentages of full monitoring variable output.
7.15 PULSE INPUT (GROUP F3.2)
F3.2.36 Min pulse input
frequency DI9/Fin
Setting range: 0.0~100.00KHz
Factory default: 0.0
F3.2.37 Max pulse input
frequencyDI9/Fin
Setting range: 0.01~100.00KHz
Factory default: 10.0
F3.2.38 Pulse detection cycle
Setting range: 1~20ms
Factory default: 10
This group of parameters defines multi-function input terminal
DI9/Fin
as frequency range and detection
cycle of external pulse signal for pulse input (
F3.0.08
is set as 97-99), effective breadth of external pulse
signal is
5-30V.
F3.2.39 Encoder pulse single channel
Setting range: 1~4096
Factory default: 1024
When input frequency signal of
DI9/Fin
terminal is used for length accumulation or speed measurement,
these parameters are used to set pulse signal quantity for each rotation of encoder.
F3.2.40 Mechanical
transmission ratio
Setting range: 0.010~10.000
Factory default: 1.000
F3.2.41 Driving wheel diameter
(for liner speed calculation)
Setting range: 0.1~2000.0mm
Factory default: 100.0
This group of parameters is used for linear speed calculation or length accumulation.
Mechanical drive ratio=rotating speed of pulse speed measuring shaft: Rotating speed of motor shaft