12 Installation Of Frequency Inverter
V260 Series High Performance Closed-Loop Vector Inverter User Manual
3.2 ASSEMBLY OF OPERATION PANEL
The name of operation panel, model, code and applicable inverter, as follows:
name
Double line LED panel
Double line LED operation
panel
(
shuttle type
)
Double line LED standard
operation panel
model DPNL350EM
DPNL360EB
DPNL360EA
code 050M007033701
050M007360004
050M007360003
Standard
model
Apply to the inverter below
V260-4T0022G/4T0030P
Apply to
V260-4T0030G/4T0040P
~
V260-4T0300G/4T0370P
Apply to the inverter above
V260-4T0370G/4T0450P
appearance
C
A
A
A
A
B
B
Right-and-left space
Align the upper part
D
D
A-50mm above
B-30mm above
C-20mm
above
D-120mm above
upper-and-lower space
Figure 3-3 Installation sizes of right and
left frequency inverters (4.0KW above)
Baffle plate
Frequency
inverter
Frequency
inverter
Figure 3-2 Installation spacing between
upper and lower frequency inverters
¾
Horizontally close installation is only for 4.0KW below, and -10
℃
~ 45
℃
environmental
temperature.
¾
For parallel installation of frequency inverters with different sizes, please carry out
installation after aligning the upper parts of all the frequency inverters, thus to be in favor
of changing cooling fan.
¾
Please don’t install frequency inverter in the environment with tattered cotton yarn and
damp dust which may cause blockage of cooling fin. If necessary to operate in such
environment, please install in the control cabinet which can keep tattered cotton yarn out.
¾
If necessary to install at the place with more than 1000m height above sea level, please
de-rate operation. See 2.4 product technical indexes and specifications for details.