Description Of Specific Functions
103
V260 Series High Performance Closed-Loop Vector Inverter User Manual
2: All keys except STOP and RUN are locked.
Only the
STOP
and
RUN
keys on the operating panel are effective.
3: All keys except STOP are locked.
Only the
STOP
key on the operating panel is effective.
4: Locking all keys
All keys are void on the operating panel.
_ _ X _ : STOP button function
0: The modes other than the panel control are void.
Only when the running command channel is the operating panel is it effective to press down the
STOP
key.
1: Press STOP key in any control mode for deceleration stop.
No matter the running command preset channel is the operating panel, external terminals or the
communication port, when
STOP
key is pressed, the inverter will control the motor to achieve deceleration
stop according to the current effective deceleration time. The priority of this stop mode is higher than that of
parameter
F0.4.38
.
2: Press STOP key in any control mode for free stop.
No matter the running command preset channel is the operating panel, external terminals or the
communication port, when
STOP
key is pressed, the inverter will stop output, and the motor stop in free
sliding mode. The priority of this stop mode is higher than that of parameter
F0.4.38
.
_ X _ _ : Function of PANEL/REMOTE keys
When the functional setting of
PANEL/REMOTE
keys is effective, and in the normal monitoring mode, the
PANEL/REMOTE
keys can be used to switch the running command channel. The switching status is not
saved, and will get lost after power-off. The running command channel for the inverter is still the operating
panel after power-on once again.
If
PANEL/REMOTE
keys are used to circularly switch to desired running command channel, it is required to
press “
OK
” key for confirmation within 5s. Otherwise, it will not get effective.
The switching sequence of the running command channel: Operating panel running command channel
(
PANEL/REMOTE
light on)
→
external terminal operating running command channel (
PANEL/REMOTE
light
off)
→
communication port running command channel (
PANEL/REMOTE
light off)
→
operating panel running
command channel (
PANEL/REMOTE
light on).
0: Void
The running command channel cannot be switched with
PANEL/REMOTE
key.
1: Effective at stop
PANEL/REMOTE
key is effective at the stop status, but it is void to switch the running command channel
with this key when the device is running.
2: Continuous effective
PANEL/REMOTE
keys can be used to switch the running command channel both at the stop and running
status.
¾
The command channel switching at the running status of the inverter should be used
carefully. Be sure the safety before operation. If the running command (FWD/REV/JOG)
after switching is inconsistent with that before switching, the inverter will change its current
running status (stop, run or REV), which may cause accident.