7.13 MULTIFUNCTIONAL INPUT TERMINAL (GROUP F3.0)
F3.0.00~F3.0.05 Multifunctional input
terminals DI1~DI6
Setting range: 0~96
——
F3.0.06 Multifunctional input terminal
DI7/ standard expansion card
Setting range: 0~96
Factory default: 0
F3.0.07 Multifunctional input terminal
DI8/ standard expansion card
Setting range: 0~96
Factory default: 0
F3.0.08 Multifunctional input terminal
DI9/Fin/standard expansion card
Setting range: 0~98
Factory default: 97
Control terminals
Dl1~Dl9/Fin
are functional programmable switch input terminals; They can define the
Dl1~Dl9/Fin
functions respectively by way of the setup of
F3.0.00~F3.0.08
values; See their set values and
relevant functions as Table 1 (Contrast Table of Multifunctional Terminals (DI/EDI/SDI) Function).
For example: Define
F3.0.00
as
23
, so the function of DI1 can be defined as "Simple
PLC
Multi-stage
Operation Input"; When the DI1 terminal status validates, simple
PLC
multi-stage operation input function
can be realized.
The function specifications in the table as following:
1~4: Multi-speed control terminals 1~4
By means of the
ON/OFF
status combinations of these four functional terminals, select the set frequencies
relevant to
F6.0.00~F6.0.15
parameters as the current set frequencies of frequency converter. The priority of
the frequency instruction is higher than frequency set channel
F0.1.16
.
Table 7-3 Multi-speed operation selection table
Multi-speed
control 4
Multi-speed
control 3
Multi-speed
control 2
Multi-speed
control 1
Frequency set
OFF OFF OFF OFF
Ordinary operation frequency
(F0.1.16 determined)
OFF OFF OFF ON
Multi-stage
operation
frequency
1
OFF
OFF
ON
OFF
Multi-stage operation frequency 2
OFF
OFF
ON
ON
Multi-stage operation frequency 3
OFF
ON
OFF
OFF
Multi-stage operation frequency 4
OFF ON OFF ON
Multi-stage
operation
frequency
5
OFF
ON
ON
OFF
Multi-stage operation frequency 6
OFF
ON
ON
ON
Multi-stage operation frequency 7
ON
OFF
OFF
OFF
Multi-stage operation frequency 8
ON OFF OFF ON
Multi-stage
operation
frequency
9
ON
OFF
ON
OFF
Multi-stage operation frequency 10
ON
OFF
ON
ON
Multi-stage operation frequency 11
ON
ON
OFF
OFF
Multi-stage operation frequency 12
ON ON OFF ON
Multi-stage
operation
frequency
13
ON ON ON OFF
Multi-stage
operation
frequency
14
ON ON ON ON
Multi-stage
operation
frequency
15