background image

28

M

INI

-S

PACE

 EC I

NSTALLATION

, O

PERATION

 

AND

 M

AINTENANCE

 M

ANUAL

4.3 Field 

Service

NOTE

Do not attempt to make repairs without the proper 
tools.

It may be necessary to perform repairs on the refrigeration 
system. If fi eld repairs are necessary, the following procedures 
apply.

4.3.1 Leak 

Detection

Several methods can be used to detect a leak in the 
refrigeration system. The most modern and easiest method is 
to use an electronic leak detector. Follow the manufacturer’s 
directions and any leak can be quickly located. A second 
method is to use soap bubbles. Apply a solution of soapy 
water with a brush or sponge to the joints and connections 
in the refrigeration lines. A leak in the lines will cause bubbles 
to form.  

NOTE

Use a halogen leak detector capable of detecting 
R410A refrigerant.

4.3.2 Leak 

Repair

When a leak is located, properly reclaim the remaining 
refrigerant charge before beginning repairs. Adjacent piping 
must be thoroughly cleaned by removing all paint, dirt and oily 
fi lm. Use a wire brush, sandcloth or sandpaper and wipe the 
area with clean, dry cloths. Protect nearby parts from heat 
damage by wrapping with water-soaked cloths.

4.3.3 Refrigerant 

Piping

When replacing components within the cabinet of the unit, 
the following solders are recommended:  Silfos alloy for 
copper-to-copper (piping discharge or suction line repairs); 
silver solder (Stay-Silv #45) and fl ux for copper-to-brass or 
copper-to-steel repairs; and a 95% tin to 5% antimony solder 
with fl ux for liquid line repairs at the drier, strainer, sight glass, 
or expansion valve.

When component replacement is complete, remove all traces 
of fl ux. After any repair, pressure check the system and ensure 
there are no leaks prior to recharging the system.

4.3.4  General Common  Repairs/Component 

Replacement

4.3.4.1 Compressor 

Failure 

The compressor is the most important component of a DX 
unit. Numerous safety devices are provided to protect the 
compressor from failing.

When a compressor fails, determine whether the cause is 
electrical or mechanical. An electrical failure is indicated by a 
distinct pungent odor once the system has been opened. If a 

burnout occurred, the oil will be black and acidic. A mechanical 
failure will have no burned odor and the motor will attempt to 
run. An abnormal or excessive noise may be present.

Analyzing the oil is the only way to determine the proper 
procedure for cleaning the refrigerant system. Acid test kits 
are available from several manufacturers for measuring the 
acid level in the oil. These are capable of making accurate 
acidity measurements, but if they are not available a check 
of the oil by sight and smell can give a quick indication if 
contamination remains in the system. Since refrigeration 
oils vary in color, a sample of the new oil in the replacement 
compressor should be removed prior to installation and sealed 
in a small glass bottle for comparison purposes. If the oil has 
been exposed to refrigerant, the bottle should not be tightly 
capped, since the residual refrigerant may create a high 
pressure if tightly sealed and exposed to high temperature.

CAUTION 

Avoid touching or contacting the gas and oil with 
exposed skin. Severe burns will result. Use long 
rubber gloves when handling contaminated parts.

All electrical connections should be checked to ensure 
they are tight and properly made. Check all circuit breakers, 
contactors and wiring. Contactors should be examined and 
replaced if the contacts are worn or pitted.

If there is acid in the oil, there has been an electrical failure 
which has caused the compressor motor to burn out. The acid 
diffuses throughout the refrigeration system and must be 
removed by using a burnout fi lter kit before a new compressor 
is placed in service. Not only must the compressor be 
replaced, but the entire refrigeration circuit must be cleaned 
of the harmful contaminants left by the burnout. See section 
4.3.4.3, “Burn-Out/Acid Cleanup Procedure”  for the proper 
procedure.

If there is no acid in the oil, there has been a mechanical failure. 
See section 4.3.4.2, “Standard Clean out Procedure”  for the 
proper cleaning procedure.

CAUTION 

Damage to a replacement compressor caused by 
improper system cleaning constitutes abuse under 
the terms of the warranty and will void the warranty.

CAUTION 

POE oil is used in systems with R410A refrigerant. If 
a replacement compressor is provided, ensure that 
it is fi lled with POE oil before installing.

Summary of Contents for SCS-018

Page 1: ...Mini Space EC DX and CW 4 12 kW Systems Vertical Floor Mounted 60 Hz Data Installation Operation and Maintenance Manual...

Page 2: ...d reproduced or translated into another language for use by anyone other than the owner of the equipment for which this manual is written without the prior written consent of STULZ Air Technology Syst...

Page 3: ...er Glycol Chilled Water and Hot Water Reheat Piping 12 2 7 3 Pump Package 12 2 7 4 Condensate Drain Line 12 2 7 4 1 Gravity Drain 12 2 7 4 2 Condensate Pump 12 2 7 5 Humidi er 12 2 8 Utility Connectio...

Page 4: ...lacement 29 4 3 4 5 Filter Replacement 30 5 0 Product Support 30 5 1 Technical Support 30 5 2 Obtaining Warranty Parts 30 5 3 Obtaining Spare Replacement Parts 31 Figures Figure 1 Typical Up ow Intern...

Page 5: ...ear return and front discharge The basic cabinet height remains the same 72 8 regardless of the con guration An optional plenum box may be selected for up owand rear return units only which adds an ex...

Page 6: ...ice or repairs WARNING Refrigerant R410A is used with this equipment Death or serious injury may result if personnel fail to observe proper safety precautions Great care must be exercised to prevent c...

Page 7: ...the front access door which is locked in three places To open the front door turn the door locks with the triangular key wrench provided The front door is also safetyinterlocked with the main power d...

Page 8: ...t output status monitoring Full integrated control of cooling Multi system control and remote communica tion with building management systems TheE controllerismountedinsidetheunitelectricbox User inte...

Page 9: ...specified otherwise by the customer The duct connection plate or plenum box if applicable are placed on top of the air conditioner inside the unit s carton Removeandstoretheseitemsinasafeplace unless...

Page 10: ...i Space EC unit is shipped on a skid to facilitate moving priorto installation The unit should always be stored indoors in a dry location prior to installation CAUTION When moving the unit it must be...

Page 11: ...g surface Locate remote condenser condensing units where the blower s are not likely to draw dirt and debris into the coil ns There should be at least 24 inches of clearance around the condenser to en...

Page 12: ...y drain pan located beneath the unit STULZ provides two types ofwater detectors installed as described below Spot type water detector Remove the protective cover and connect two control wires totheter...

Page 13: ...ce between the evaporator and the condenser condensingunit Eachvalve ttingandbendinthe refrigerant line must be considered in this calculation Refer to the following chart provided for determining the...

Page 14: ...OTTOM DISCHARGE TOP FREE RETURN BOTTOM DISCHARGE RETURN AIR INLET SUPPLY AIR OUTLET TOP DUCTED RETURN BOTTOM DISCHARGE SUPPLY AIR OUTLET RETURN AIR INLET DUCT RETURN AIR INLET SUPPLY AIR OUTLET RETURN...

Page 15: ...atterns SUPPLY AIR OUTLET RETURN AIR INLET SUPPLY AIR OUTLET DUCT RETURN AIR INLET REAR DUCTED RETURN SUPPLY AIR OUTLET DUCT RETURN AIR INLET FRONT FREE RETURN DUCT RETURN AIR INLET SUPPLY AIR OUTLET...

Page 16: ...e discharge line to prevent back ow that may damage the pump on shut down Install a ball valve in the suction and discharge lines for maintenance purposes 2 7 4 Condensate Drain Line 2 7 4 1 Gravity D...

Page 17: ...nimum circuit ampacity MCA forwire sizing andthe maximumfuse or HACR Heating Air Conditioning Refrigeration breaker size MAX FUSE CKT BKR for circuit protection The unit s nameplateislocatedinsidethec...

Page 18: ...ires are connected in this manner A ground lug is provided in each unit nearthe non fused main powerdisconnect switch Prior to unit operation an adequate unit to earth ground must be connected to the...

Page 19: ...aller must also wire control conductors from the terminal board in the A C unit to the control terminal board in the remote condenser electric box Refer to the electrical drawing forthe correct number...

Page 20: ...IN POWER SUPPLY 208 460V 1PH 3PH 60Hz MODELS CC 041 121 W G INTERCONNECTING FIELD WIRING TO BE INSTALLED IN ACCORDANCE WITH NFPA 70 N E C L3 L1 L2 Figure 10 Interconnecting Field Wiring Remote Condens...

Page 21: ...luding newly installedorexistingpiping Thepumpmustbeingood operating condition Ensure it contains clean fresh oil Manufacturers recommend you change the oil in the pump regularly to maintain its abili...

Page 22: ...cess of evacuating the system this time with a goal of achieving a 250 micron vacuum or less Close the vacuum pump isolation valve Whenyou can hold thevacuum at 500 microns or lower for at least 2 hou...

Page 23: ...CAUTION Remove the blockage from the air intake of the condenser 10 Fill out the applicable sections of the Warranty Regis tration and Start Up Checklist 2 9 4 4 30 F Ambient Applications NOTE For un...

Page 24: ...to ow from the condenser to the receiver When using this method of head pressure regulation there mustbeenoughrefrigerantinthesystemtoensureadequate chargeatthelowestexpectedambienttemperatureinwhich...

Page 25: ...suction low side of the compressor as it operates in full hot gas bypass operation The valve is factory set and noadjustmentshouldbenecessary Ifadjustmentisrequired blockonehalfofthecoilandremoveadju...

Page 26: ...rs might be requiredto see adesired level orrise ofhumid ityinthe conditioned space Once room conditions have beenprogrammedorset arepeatvisittotheconditioned site may be required to ensure the humidi...

Page 27: ...R410A refrigerant is exposed to flame Always ensure adequate ventilation during refrigeration repairs WARNING Always recover all refrigerant prior to any system repairs Failure to do so may result in...

Page 28: ...r a long period do not attempt to start the condensing unit until eight hours after applyingpower Thisallowsenoughtimeforallliquid refrigerant to be driven out of the compressor This is especially imp...

Page 29: ...k for and clear any obstructions across or in the supply discharge air stream 3 Check correct rotation of evaporator blower b Temperature setting too low Increase temperature setpoint 68 F min c Disch...

Page 30: ...rior to adding to system Remove solution and premix Re ll system Condenser Pressure Too Low a Loss of refrigerant indicated by bubbles in sight glass Locate and repair leak Recharge system b Condenser...

Page 31: ...ated Check for supply registers that may be too close to thermostat Relocate if necessary Heater Inoperative a Fuses blown Check for short circuit replace fuse b Temperature set too low Increase tempe...

Page 32: ...een opened Ifa burnoutoccurred theoilwillbeblackandacidic Amechanical failurewill have no burned odorandthe motorwill attemptto run An abnormal or excessive noise may be present Analyzing the oil is t...

Page 33: ...system through the access valve on the suction line lter drier 8 Turn on power at the main power disconnect switch and start the system at the controller 9 Thepermanentlyinstalledsuctionline lter drie...

Page 34: ...Technical Support Department is dedicated to the prompt reply and resolution of issues experienced with supplied equipment Please contact 888 529 1266 Monday through Friday from 8 00 a m to 5 00 p m...

Page 35: ...ntplaceontheexternalpackaging of the returned part 5 3 Obtaining Spare Replacement Parts Maintaining a recommended spare parts inventory is an industrybestpracticeforcriticalfacilities On sitespareski...

Page 36: ...ean Condensate Pump Annually Refrigerant Systems Chilled Water Systems Inspect Glycol System for Leaks and Corrosion Inspect Chilled Water System for Leaks and Corrosion Conduct a Complete Check of Al...

Page 37: ...uality in w g Inches of Water Gauge kVA Kilo Volt Amps kW Kilowatt LEWT Low Entering Water Temperature LRA Locked Rotor Amps MAX CKT BKR Maximum Circuit Breaker MAX FUSE Maximum Fuse MCA Minimum Circu...

Page 38: ...34 MINI SPACE EC INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes...

Page 39: ...35 MINI SPACE EC INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes...

Page 40: ...1034 28918 Legan s Madrid STULZ France S A R L 107 Chemin de Ronde 78290 Croissy sur Seine info stulz fr STULZ S p A Via Torricelli 3 37067 Valeggio sul Mincio VR STULZ CHSPL India Pvt Ltd 006 Jagrut...

Reviews: