background image

29

M

INI

-S

PACE

 EC I

NSTALLATION

, O

PERATION

 

AND

 M

AINTENANCE

 M

ANUAL

4.3.4.2 

 Standard Clean out Procedure

NOTE

Cleaning operations must be performed by a 
journeyman refrigeration mechanic or air conditioning 
technician.

1.  Turn off power to unit at the main power disconnect 

switch.

2.  Remove the old compressor and install the new com-

pressor.

3.  Remove the liquid line drier and install an oversized 

liquid line fi lter-drier (one size larger than the normal 
selection size).

4.  Evacuate the system according to standard procedures. 

Normally, this will include the use of a high-vacuum 
pump and a low-vacuum micron gauge for measuring 
the vacuum obtained.

5. Recharge 

the 

system.

6.  Turn on the power at the main power disconnect switch 

and start the system at the controller.

4.3.4.3 

 Burn-Out/Acid Cleanup Procedure

The unit should be cleaned using the suction line fi lter-drier 
method.

CAUTION 

Avoid touching or contacting the gas and oil with 
exposed skin. Severe burns will result. Use long 
rubber gloves in handling contaminated parts.

NOTE

Cleaning operations must be performed by a 
journeyman refrigeration mechanic or air conditioning 
technician.

1.  Turn off power to the unit at the main power disconnect 

switch.

2.  Remove the burned out compressor and install the new 

compressor.

3.   Install a suction line fi lter-drier designed for acid removal.

4.  Remove the liquid line drier and install an oversized liquid 

line fi lter-drier (one size larger than the normal size for 
the unit).

5.  Check the expansion valve, sight glass and other controls 

to see if cleaning or replacement is required.

6.  Evacuate the system according to standard procedures. 

Normally, this will include the use of a high-vacuum 
pump and a low-vacuum micron gauge for measuring 
the vacuum obtained.

7.  Recharge the system through the access valve on the 

suction line fi lter-drier.

8.  Turn on power at the main power disconnect switch and 

start the system at the controller.

9.  The permanently installed suction line fi lter-drier permits 

small system cleanup to be completed in one service 
call. The pressure drop across the suction line fi lter-drier 
should be measured during the fi rst hour of operation. If 
the pressure drop becomes excessive, the suction line 
fi lter-drier should be replaced (See Sporlan Bulletin 40-
10, for the maximum recommended pressure drop (PSI) 
for the suction line fi lter drier).

10.  In 24 hours, take an oil sample. Observe the color and 

test for acidity. If the oil is dirty or acidic, replace the suc-
tion line fi lter-drier.

11.  In 2 weeks, examine oil to determine if another suction 

line fi lter-drier change is necessary.

4.3.4.4  

Humidifi er Cylinder Replacement

The cylinder is disposable and cylinder life is dependent 
on water supply conditions and humidifi er usage. After an 
extended period of operation a yellow LED on the humidifi er 
cabinet will fl ash in a four-fl ash sequence to indicate the 
cylinder is completely used and a replacement cylinder must 
be installed. The following procedures should be followed 
when replacing the cylinder.

CAUTION 

Failure to replace cylinder at the end of cylinder life 
may result in humidifi er damage.

NOTE

Decrease the low humidity setpoint below ambient 
humidity to allow the cylinder to cool down before 
removing the cylinder.

1.  Turn the unit off, preferably in a manner that uses the 

controller, such as via the graphic controller, BMS or 
external shutdown control. 

2.  Drain the cylinder by switching the “On/Off/Drain” switch 

to the “Drain” position. Let the humidifi er drain until no 
more water is fl owing out to drain (usually not more than 
10 minutes).

3. Turn 

the 

humidifi er On/Off/Drain switch to off.

4.  Turn off water supply to the humidifi er.

5.  Exit the cabinet and disconnect power to the humidifi er 

at the main power disconnect switch.

Summary of Contents for SCS-018

Page 1: ...Mini Space EC DX and CW 4 12 kW Systems Vertical Floor Mounted 60 Hz Data Installation Operation and Maintenance Manual...

Page 2: ...d reproduced or translated into another language for use by anyone other than the owner of the equipment for which this manual is written without the prior written consent of STULZ Air Technology Syst...

Page 3: ...er Glycol Chilled Water and Hot Water Reheat Piping 12 2 7 3 Pump Package 12 2 7 4 Condensate Drain Line 12 2 7 4 1 Gravity Drain 12 2 7 4 2 Condensate Pump 12 2 7 5 Humidi er 12 2 8 Utility Connectio...

Page 4: ...lacement 29 4 3 4 5 Filter Replacement 30 5 0 Product Support 30 5 1 Technical Support 30 5 2 Obtaining Warranty Parts 30 5 3 Obtaining Spare Replacement Parts 31 Figures Figure 1 Typical Up ow Intern...

Page 5: ...ear return and front discharge The basic cabinet height remains the same 72 8 regardless of the con guration An optional plenum box may be selected for up owand rear return units only which adds an ex...

Page 6: ...ice or repairs WARNING Refrigerant R410A is used with this equipment Death or serious injury may result if personnel fail to observe proper safety precautions Great care must be exercised to prevent c...

Page 7: ...the front access door which is locked in three places To open the front door turn the door locks with the triangular key wrench provided The front door is also safetyinterlocked with the main power d...

Page 8: ...t output status monitoring Full integrated control of cooling Multi system control and remote communica tion with building management systems TheE controllerismountedinsidetheunitelectricbox User inte...

Page 9: ...specified otherwise by the customer The duct connection plate or plenum box if applicable are placed on top of the air conditioner inside the unit s carton Removeandstoretheseitemsinasafeplace unless...

Page 10: ...i Space EC unit is shipped on a skid to facilitate moving priorto installation The unit should always be stored indoors in a dry location prior to installation CAUTION When moving the unit it must be...

Page 11: ...g surface Locate remote condenser condensing units where the blower s are not likely to draw dirt and debris into the coil ns There should be at least 24 inches of clearance around the condenser to en...

Page 12: ...y drain pan located beneath the unit STULZ provides two types ofwater detectors installed as described below Spot type water detector Remove the protective cover and connect two control wires totheter...

Page 13: ...ce between the evaporator and the condenser condensingunit Eachvalve ttingandbendinthe refrigerant line must be considered in this calculation Refer to the following chart provided for determining the...

Page 14: ...OTTOM DISCHARGE TOP FREE RETURN BOTTOM DISCHARGE RETURN AIR INLET SUPPLY AIR OUTLET TOP DUCTED RETURN BOTTOM DISCHARGE SUPPLY AIR OUTLET RETURN AIR INLET DUCT RETURN AIR INLET SUPPLY AIR OUTLET RETURN...

Page 15: ...atterns SUPPLY AIR OUTLET RETURN AIR INLET SUPPLY AIR OUTLET DUCT RETURN AIR INLET REAR DUCTED RETURN SUPPLY AIR OUTLET DUCT RETURN AIR INLET FRONT FREE RETURN DUCT RETURN AIR INLET SUPPLY AIR OUTLET...

Page 16: ...e discharge line to prevent back ow that may damage the pump on shut down Install a ball valve in the suction and discharge lines for maintenance purposes 2 7 4 Condensate Drain Line 2 7 4 1 Gravity D...

Page 17: ...nimum circuit ampacity MCA forwire sizing andthe maximumfuse or HACR Heating Air Conditioning Refrigeration breaker size MAX FUSE CKT BKR for circuit protection The unit s nameplateislocatedinsidethec...

Page 18: ...ires are connected in this manner A ground lug is provided in each unit nearthe non fused main powerdisconnect switch Prior to unit operation an adequate unit to earth ground must be connected to the...

Page 19: ...aller must also wire control conductors from the terminal board in the A C unit to the control terminal board in the remote condenser electric box Refer to the electrical drawing forthe correct number...

Page 20: ...IN POWER SUPPLY 208 460V 1PH 3PH 60Hz MODELS CC 041 121 W G INTERCONNECTING FIELD WIRING TO BE INSTALLED IN ACCORDANCE WITH NFPA 70 N E C L3 L1 L2 Figure 10 Interconnecting Field Wiring Remote Condens...

Page 21: ...luding newly installedorexistingpiping Thepumpmustbeingood operating condition Ensure it contains clean fresh oil Manufacturers recommend you change the oil in the pump regularly to maintain its abili...

Page 22: ...cess of evacuating the system this time with a goal of achieving a 250 micron vacuum or less Close the vacuum pump isolation valve Whenyou can hold thevacuum at 500 microns or lower for at least 2 hou...

Page 23: ...CAUTION Remove the blockage from the air intake of the condenser 10 Fill out the applicable sections of the Warranty Regis tration and Start Up Checklist 2 9 4 4 30 F Ambient Applications NOTE For un...

Page 24: ...to ow from the condenser to the receiver When using this method of head pressure regulation there mustbeenoughrefrigerantinthesystemtoensureadequate chargeatthelowestexpectedambienttemperatureinwhich...

Page 25: ...suction low side of the compressor as it operates in full hot gas bypass operation The valve is factory set and noadjustmentshouldbenecessary Ifadjustmentisrequired blockonehalfofthecoilandremoveadju...

Page 26: ...rs might be requiredto see adesired level orrise ofhumid ityinthe conditioned space Once room conditions have beenprogrammedorset arepeatvisittotheconditioned site may be required to ensure the humidi...

Page 27: ...R410A refrigerant is exposed to flame Always ensure adequate ventilation during refrigeration repairs WARNING Always recover all refrigerant prior to any system repairs Failure to do so may result in...

Page 28: ...r a long period do not attempt to start the condensing unit until eight hours after applyingpower Thisallowsenoughtimeforallliquid refrigerant to be driven out of the compressor This is especially imp...

Page 29: ...k for and clear any obstructions across or in the supply discharge air stream 3 Check correct rotation of evaporator blower b Temperature setting too low Increase temperature setpoint 68 F min c Disch...

Page 30: ...rior to adding to system Remove solution and premix Re ll system Condenser Pressure Too Low a Loss of refrigerant indicated by bubbles in sight glass Locate and repair leak Recharge system b Condenser...

Page 31: ...ated Check for supply registers that may be too close to thermostat Relocate if necessary Heater Inoperative a Fuses blown Check for short circuit replace fuse b Temperature set too low Increase tempe...

Page 32: ...een opened Ifa burnoutoccurred theoilwillbeblackandacidic Amechanical failurewill have no burned odorandthe motorwill attemptto run An abnormal or excessive noise may be present Analyzing the oil is t...

Page 33: ...system through the access valve on the suction line lter drier 8 Turn on power at the main power disconnect switch and start the system at the controller 9 Thepermanentlyinstalledsuctionline lter drie...

Page 34: ...Technical Support Department is dedicated to the prompt reply and resolution of issues experienced with supplied equipment Please contact 888 529 1266 Monday through Friday from 8 00 a m to 5 00 p m...

Page 35: ...ntplaceontheexternalpackaging of the returned part 5 3 Obtaining Spare Replacement Parts Maintaining a recommended spare parts inventory is an industrybestpracticeforcriticalfacilities On sitespareski...

Page 36: ...ean Condensate Pump Annually Refrigerant Systems Chilled Water Systems Inspect Glycol System for Leaks and Corrosion Inspect Chilled Water System for Leaks and Corrosion Conduct a Complete Check of Al...

Page 37: ...uality in w g Inches of Water Gauge kVA Kilo Volt Amps kW Kilowatt LEWT Low Entering Water Temperature LRA Locked Rotor Amps MAX CKT BKR Maximum Circuit Breaker MAX FUSE Maximum Fuse MCA Minimum Circu...

Page 38: ...34 MINI SPACE EC INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes...

Page 39: ...35 MINI SPACE EC INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes...

Page 40: ...1034 28918 Legan s Madrid STULZ France S A R L 107 Chemin de Ronde 78290 Croissy sur Seine info stulz fr STULZ S p A Via Torricelli 3 37067 Valeggio sul Mincio VR STULZ CHSPL India Pvt Ltd 006 Jagrut...

Reviews: