background image

12

M

INI

-S

PACE

 EC I

NSTALLATION

, O

PERATION

 

AND

 M

AINTENANCE

 M

ANUAL

Consult the Copeland applications data guide for detailed 
information regarding refrigerant line traps and line sizing.

2.7.2  Water/Glycol, Chilled Water and Hot 

Water Reheat Piping

The piping connections for water/glycol and chilled 
water systems are sweat connections. Pipe sizes may not 
necessarily be the same size as the unit connection. Piping 
should be sized to match the required system pressure drop 
and pump capacity (if applicable) and may require reducing 
fi ttings to match the connection size on the air conditioner. 

Water/glycol/chilled water-cooled systems with low 
entering fl uid temperatures should have insulated piping. 
The recommended ethylene glycol solution ratio is 40% 
glycol to 60% water. (STULZ recommends Dowtherm SR1 
manufactured by Dow Chemical Co.) Use only ethylene glycol 
with inhibitors for corrosion protection. 

WARNING 

Glycol is hazardous. Consult the manufacturer’s SDS 
for detailed safety information.

CAUTION 

When installing and fi lling the water/glycol/chilled 
water loop and optional hot water reheat loop, all air 
must be bled from the piping system.

CAUTION 

 

The piping system must be fl ushed prior to operating 
the system. Failure to do so will result in equipment 
problems.

A strainer should be included in the water/glycol/chilled water 
line. Once the system is operational, the fl uid runs through the 
strainer where any foreign objects are removed. The strainer 
screen should be cleaned periodically.

2.7.3 Pump 

Package

Install a concentric reducer at the pump suction and discharge 
openings and make all piping at least one (1) size larger than 
the diameter of the openings. If a suction strainer is necessary, 
install one with a net area 2

3 times larger than the suction 

piping. The piping leaving the drycooler should enter the 
pump suction port. Install a check valve in the discharge line 
to prevent back fl ow that may damage the pump on shut 
down.  Install a ball valve in the suction and discharge lines 
for maintenance purposes.

2.7.4  Condensate Drain Line

2.7.4.1 Gravity 

Drain

A drain line is installed to drain the condensate pan. If an 
optional humidifi er is used, the drain line from the humidifi er is 
typically connected to the condensate drain line. The drain line 
is run out of the right side of the cabinet. See the installation 
drawing provided with your unit for the size and location of 
the condensate drain line.

NOTE

The humidifi er drains (hot) water into the condensate 
drain line during normal operation. As an option, 
a separate drain line may be provided for the 
humidifi er.

The drain line must not be exposed to freezing temperatures. 
The diameter of the drain line should be the full size of the 
 connection.

NOTE

Pour some water into the condensate drain pan(s) 
prior to start-up. This fi lls the trap and prevents air 
from being drawn up the drain lines.

2.7.4.2 Condensate 

Pump

An optional condensate pump shown in Figure 7 on page 
13 is available for automatic removal of condensate from 
the air conditioner and fl ush water from the humidifi er. The 
condensate pump must be fi eld installed.

A P-trap is installed in the condensate pan drain line, so one is 
not required for the condensate pump. The condensate pump 
discharge line should be 1/2 inch OD (maximum) copper 
pipe to prevent excessive backfl ow to the condensate pump.

2.7.5 Humidifi er 

Mini-Space EC systems use an electrode steam humidifi er. In 
most cases the humidifi er empties into the condensate drain 
line during the fl ush/drain cycle. As an option, the drain for 
the humidifi er may have a separate connection. Refer to the 
installation drawing provided with your unit for the size and 
location of the connection.

Table 3.  

 Recommended Discharge Line Sizes

Recommended Discharge Line Sizes

(For R410A Refrigerant)

CC() Model 

No./Total

BTU Capacity

Equivalent Length Ft*

50’ or less

100’ or less

150’ or less

041 / 12,000

1/2

1/2

5/8

061 / 18,000

5/8

5/8

5/8

081 / 24,000

5/8

7/8

7/8

121 / 36,000

7/8

7/8

7/8

Summary of Contents for SCS-018

Page 1: ...Mini Space EC DX and CW 4 12 kW Systems Vertical Floor Mounted 60 Hz Data Installation Operation and Maintenance Manual...

Page 2: ...d reproduced or translated into another language for use by anyone other than the owner of the equipment for which this manual is written without the prior written consent of STULZ Air Technology Syst...

Page 3: ...er Glycol Chilled Water and Hot Water Reheat Piping 12 2 7 3 Pump Package 12 2 7 4 Condensate Drain Line 12 2 7 4 1 Gravity Drain 12 2 7 4 2 Condensate Pump 12 2 7 5 Humidi er 12 2 8 Utility Connectio...

Page 4: ...lacement 29 4 3 4 5 Filter Replacement 30 5 0 Product Support 30 5 1 Technical Support 30 5 2 Obtaining Warranty Parts 30 5 3 Obtaining Spare Replacement Parts 31 Figures Figure 1 Typical Up ow Intern...

Page 5: ...ear return and front discharge The basic cabinet height remains the same 72 8 regardless of the con guration An optional plenum box may be selected for up owand rear return units only which adds an ex...

Page 6: ...ice or repairs WARNING Refrigerant R410A is used with this equipment Death or serious injury may result if personnel fail to observe proper safety precautions Great care must be exercised to prevent c...

Page 7: ...the front access door which is locked in three places To open the front door turn the door locks with the triangular key wrench provided The front door is also safetyinterlocked with the main power d...

Page 8: ...t output status monitoring Full integrated control of cooling Multi system control and remote communica tion with building management systems TheE controllerismountedinsidetheunitelectricbox User inte...

Page 9: ...specified otherwise by the customer The duct connection plate or plenum box if applicable are placed on top of the air conditioner inside the unit s carton Removeandstoretheseitemsinasafeplace unless...

Page 10: ...i Space EC unit is shipped on a skid to facilitate moving priorto installation The unit should always be stored indoors in a dry location prior to installation CAUTION When moving the unit it must be...

Page 11: ...g surface Locate remote condenser condensing units where the blower s are not likely to draw dirt and debris into the coil ns There should be at least 24 inches of clearance around the condenser to en...

Page 12: ...y drain pan located beneath the unit STULZ provides two types ofwater detectors installed as described below Spot type water detector Remove the protective cover and connect two control wires totheter...

Page 13: ...ce between the evaporator and the condenser condensingunit Eachvalve ttingandbendinthe refrigerant line must be considered in this calculation Refer to the following chart provided for determining the...

Page 14: ...OTTOM DISCHARGE TOP FREE RETURN BOTTOM DISCHARGE RETURN AIR INLET SUPPLY AIR OUTLET TOP DUCTED RETURN BOTTOM DISCHARGE SUPPLY AIR OUTLET RETURN AIR INLET DUCT RETURN AIR INLET SUPPLY AIR OUTLET RETURN...

Page 15: ...atterns SUPPLY AIR OUTLET RETURN AIR INLET SUPPLY AIR OUTLET DUCT RETURN AIR INLET REAR DUCTED RETURN SUPPLY AIR OUTLET DUCT RETURN AIR INLET FRONT FREE RETURN DUCT RETURN AIR INLET SUPPLY AIR OUTLET...

Page 16: ...e discharge line to prevent back ow that may damage the pump on shut down Install a ball valve in the suction and discharge lines for maintenance purposes 2 7 4 Condensate Drain Line 2 7 4 1 Gravity D...

Page 17: ...nimum circuit ampacity MCA forwire sizing andthe maximumfuse or HACR Heating Air Conditioning Refrigeration breaker size MAX FUSE CKT BKR for circuit protection The unit s nameplateislocatedinsidethec...

Page 18: ...ires are connected in this manner A ground lug is provided in each unit nearthe non fused main powerdisconnect switch Prior to unit operation an adequate unit to earth ground must be connected to the...

Page 19: ...aller must also wire control conductors from the terminal board in the A C unit to the control terminal board in the remote condenser electric box Refer to the electrical drawing forthe correct number...

Page 20: ...IN POWER SUPPLY 208 460V 1PH 3PH 60Hz MODELS CC 041 121 W G INTERCONNECTING FIELD WIRING TO BE INSTALLED IN ACCORDANCE WITH NFPA 70 N E C L3 L1 L2 Figure 10 Interconnecting Field Wiring Remote Condens...

Page 21: ...luding newly installedorexistingpiping Thepumpmustbeingood operating condition Ensure it contains clean fresh oil Manufacturers recommend you change the oil in the pump regularly to maintain its abili...

Page 22: ...cess of evacuating the system this time with a goal of achieving a 250 micron vacuum or less Close the vacuum pump isolation valve Whenyou can hold thevacuum at 500 microns or lower for at least 2 hou...

Page 23: ...CAUTION Remove the blockage from the air intake of the condenser 10 Fill out the applicable sections of the Warranty Regis tration and Start Up Checklist 2 9 4 4 30 F Ambient Applications NOTE For un...

Page 24: ...to ow from the condenser to the receiver When using this method of head pressure regulation there mustbeenoughrefrigerantinthesystemtoensureadequate chargeatthelowestexpectedambienttemperatureinwhich...

Page 25: ...suction low side of the compressor as it operates in full hot gas bypass operation The valve is factory set and noadjustmentshouldbenecessary Ifadjustmentisrequired blockonehalfofthecoilandremoveadju...

Page 26: ...rs might be requiredto see adesired level orrise ofhumid ityinthe conditioned space Once room conditions have beenprogrammedorset arepeatvisittotheconditioned site may be required to ensure the humidi...

Page 27: ...R410A refrigerant is exposed to flame Always ensure adequate ventilation during refrigeration repairs WARNING Always recover all refrigerant prior to any system repairs Failure to do so may result in...

Page 28: ...r a long period do not attempt to start the condensing unit until eight hours after applyingpower Thisallowsenoughtimeforallliquid refrigerant to be driven out of the compressor This is especially imp...

Page 29: ...k for and clear any obstructions across or in the supply discharge air stream 3 Check correct rotation of evaporator blower b Temperature setting too low Increase temperature setpoint 68 F min c Disch...

Page 30: ...rior to adding to system Remove solution and premix Re ll system Condenser Pressure Too Low a Loss of refrigerant indicated by bubbles in sight glass Locate and repair leak Recharge system b Condenser...

Page 31: ...ated Check for supply registers that may be too close to thermostat Relocate if necessary Heater Inoperative a Fuses blown Check for short circuit replace fuse b Temperature set too low Increase tempe...

Page 32: ...een opened Ifa burnoutoccurred theoilwillbeblackandacidic Amechanical failurewill have no burned odorandthe motorwill attemptto run An abnormal or excessive noise may be present Analyzing the oil is t...

Page 33: ...system through the access valve on the suction line lter drier 8 Turn on power at the main power disconnect switch and start the system at the controller 9 Thepermanentlyinstalledsuctionline lter drie...

Page 34: ...Technical Support Department is dedicated to the prompt reply and resolution of issues experienced with supplied equipment Please contact 888 529 1266 Monday through Friday from 8 00 a m to 5 00 p m...

Page 35: ...ntplaceontheexternalpackaging of the returned part 5 3 Obtaining Spare Replacement Parts Maintaining a recommended spare parts inventory is an industrybestpracticeforcriticalfacilities On sitespareski...

Page 36: ...ean Condensate Pump Annually Refrigerant Systems Chilled Water Systems Inspect Glycol System for Leaks and Corrosion Inspect Chilled Water System for Leaks and Corrosion Conduct a Complete Check of Al...

Page 37: ...uality in w g Inches of Water Gauge kVA Kilo Volt Amps kW Kilowatt LEWT Low Entering Water Temperature LRA Locked Rotor Amps MAX CKT BKR Maximum Circuit Breaker MAX FUSE Maximum Fuse MCA Minimum Circu...

Page 38: ...34 MINI SPACE EC INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes...

Page 39: ...35 MINI SPACE EC INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes...

Page 40: ...1034 28918 Legan s Madrid STULZ France S A R L 107 Chemin de Ronde 78290 Croissy sur Seine info stulz fr STULZ S p A Via Torricelli 3 37067 Valeggio sul Mincio VR STULZ CHSPL India Pvt Ltd 006 Jagrut...

Reviews: