3
/11.2015/
electric_MS
EN
Requirements
:
- Network configuration TN-S, TN-C-S (400V +/-10%, 3 phases, N, PE,
50/60 Hz)
- The housing is intended only for indoor installation.
- Use only copper conductors for 75°C.
- Install two back-up fuses in the supply lines.The size of the back-up fuses
depends on the terminal equipment (A/C unit).
- Choose the cable cross-sections in accordance with local standards, the
laying method and line lengths.
main switch
A
40
63
80
single-wire or multi-wire
mm²
16
16
50
finely stranded conductor
mm²
16
16
35
Maximum cross-section of the supply lines
cable introduction