EN/01.2010/
reheat
/1
The reheat is an optional extra for your A/C unit. It is installed complete and integrated in the function and method
of operation of the A/C unit. It is used to heat up the air. The following versions of the heater are available:
- Electrical reheat
- Hot water reheat (HW)
- Hotgas reheat (HG)
Electrical reheat
HW reheat
HG reheat
The reheat is connected in accordance
with the electric diagram. It is cont-
rolled and monitored by the controller.
The values for switching on and off are
adjusted in the "operate/components/
heating" menu on the controller. Refer
to the operating instructions C7000.
C1002: menu item 12-14 (E, F, H)
C6000: Control/module functions/He-
ating/E-heating
The HW reheat is to be connected
to an external hot water circuit.
The water supply is controlled via
an electrically actuated HW valve.
The HW valve is controlled via the
controller. The control parameters
are adjusted in the "operate/compo-
nents/heating/HWR valve" menu on
the controller. Refer to the operating
instructions C7000.
C1002: menu item 12-14 (E, F, H)
C6000: Control/module functions/
Heating/HWR-valve
The hotgas reheat is integrated in
the refrigerant circuit in accordance
with the refrigerant diagram in the
appendix. The refrigerant supply is
controlled via an electrically-actuated
3-way solenoid valve. The solenoid
valve is controlled via the controller.
The control parameters are adjusted
in the "operate/components/heating"
menu on the controller. Refer to the
operating instructions C7000.
C1002: menu item 12-14 (E, F, H)
Operation
The reheat is controlled and monitored by the controller. No further measures are required for operation.
Maintenance
Clean the reheat annually from contaminations and check it for damage.
12.2 Reheat
Description
Cabinet size 1
Cabinet size 2
Summary of Contents for Mini-Space DX CCD131A
Page 13: ...07 2016 G20 13 EN 5 3 Dimensional drawings Cabinet size 1 Cabinet size 2...
Page 36: ......
Page 58: ...10 01 2017 air_MSDX 150 1000 810 700 160 920 EN Size 2 Filter top with flexible duct...
Page 62: ......
Page 66: ......
Page 70: ......
Page 73: ......