The A/C unit may only be dismantled by qualified specialists.
• switch off the A/C unit at the controller and at the master switch.
• switch off power conducting cables to the unit and secure them against being switched on again.
dAngeR
Mortal danger by electric hazard
At the fan contactor, dangerous voltages occur. Do not open the unit within the first 5 minutes
after disconnection of all phases.
In units with 2 fans dangerous charges of >50µC can occur between AC line terminals and PE
after disconnection.
• disconnect the A/C unit from the de-energized network.
CAUtion
If glycol or similar additives had been used, this liquid has to be collected and disposed in an
appropriate manner and may under no circumstances be introduced in the local waste water
system.
• disconnect the unit from the external water circuit by closing the shut-off valves and drain the water circuit
of the unit.
• disconnect the depressurized chilled water pipes of the unit from the external system.
• move the unit, as described in the chapter „transport“, with a lifting device of sufficient load-carrying
capacity.
• dispose of the A/C unit in accordance with the disposal and safety regulations applicable on site.
We recommend a recycling company for this. The unit basically contains the raw materials aluminium (heat
exchanger), copper (pipelines, wiring), and iron (panelling).