40
Cyberair mini Cw originaL instruCtions
EN/06.2021/G23 © STULZ GmbH – all rights reserved
WARning
Risk of injury by burns and rotation
The electronics housing of the fan motor can get hot.
The fans have an operation delay after the unit is stopped !
CAUtion
injury to the eyes by dust and dirt
Before starting the unit, make sure that no person is at the outlet area of the fan. The outlet area
is in the raised floor for downflow units and above the unit for upflow units.
CAUtion
Fracture or loss of limbs
The running fan can suck in and draw in loose clothing.
Before starting the unit, make sure that there is no person at the inlet area of the fan. In upflow
units the inlet area is only accessible when the rear panels are removed.
Fan
The bearings of the fans are lifetime lubricated and do not need maintenance.
• Check the operation current. An increased operation current indicates a winding short circuit in the fan
motor.