3
© STULZ GmbH – all rights reserved EN/04.2021
raised floor stand
Other mounting options (e.g. louvers)
If a damper shall be installed beneath the unit, this must be first mounted onto the adapter plate.
• route the cable through the knock out hole to the top.
• install the damper actuator on the shaft, so that it will be on the left unit side.
Positioning of the A/C unit on the floor stand
When positioning the A/C unit on the floor stand, it must be brought precisely into the correct position above
the floor stand from the front (under no circumstances diagonally).
• use mounting aids to bring in the unit and
secure these by fixing belts at the A/C unit.
• lay at least two securing instruments (e. g.
square steel bars) on the stand to avoid a
slip-off.
• when the unit is in the right position take away
the securing aids and set down the unit.
• now pull away the mounting aids under the
unit.
when distance Z
> 100 mm
when distance Z < 100 mm
Detail of raised floor connection
Raised floor stand
Adjustable support plate
Adjusting nut
Support pipe
Support base
Mafund plate
Raised floor cut out angle
Continuous seal profile
(use closed-cell material only)
Before unit installation
Raised floor plate
Angled bracket
Permanently elastic seal
Fixing
1
2
3
4
5
6
7
8
9
10
11
12
13
Mounting aid