16
EN/06.2021 © STULZ GmbH – all rights reserved
air side connection
wArning
Risk of bruising of limbs
Check that the power supply to the A/C unit is switched off so that the damper cannot be
started.
wArning
Risk of bruising of limbs
Do not insert fingers between the damper blades or near the gears.
Operation
The damper is controlled by the EcoCool function of the controller.
Installation
• Place the mounting rail, which is supplied loose
with the FCP, on the rear cross strut of the A/C
unit.
• Secure the mounting rail to the cross strut with
the enclosed self-tapping screws (Size 1: 3
screws, size 2: 4, sizes 3-4: 5).
To place the FCP on the A/C unit, you need another
person due to the weight.
The cable is already connected in the E-box and
routed on the left side wall and lies rolled up on the
filter element.
• Place the FCP on the A/C unit.
• Push the FCP into the mounting rail from the
front.
• Lift the FCP at the front by 150-200 mm and
place it on square timbers. Feed the cable end
through an opening at the top left rear.
• Fix the cable with the cable ties on arrowhead.
• Pull the cable from the outside.
• Check that the cable inside the FCP is not pulled
too tight.
• Remove the square timbers and place the FCP
front side on the A/C unit.
• Cut the cable to length and connect it to the
switch box according to the electric diagram.
• Screw the FCP to the front cross strut with the
remaining self-tapping screws.
(Size 1: 3 screws, size 2: 4, sizes 3-4: 5).
Mounting rail
Switch box
• Install the fresh air connection (e.g. in the form of a duct) to the rear damper. For the dimensions of the
damper, see the previous page.
Outside air
damper
Cable which must be
connected
See notes on page 9.