5.2 Positioning the unit
You will need two mounting aids as shown below.
When placing the unit on a raised floor stand, this must be installed first. Refer to the instructions in the chap-
ter „Raised floor stand“.
WArnInG
risk of crushing limbs
A defective lifting device can lead to the uncontrolled fall of the A/C unit.
Do not stay under suspended loads! Wear safety boots, safety gloves and helmet.
Mounting aids
Pallet height
Transport with a fork lift
• transport the A/C unit on the pallet as close
as possible to the installation site.
• unscrew transport lock (2 metal angles) from
the pallet.
• adjust the mounting aids at the left and right
unit side to pallet height.
• push mounting aids under left and right side
of the unit.
• secure the mounting aids by belts around the
unit.
• lift the A/C unit.
• remove the pallet.
• drive the unit by the mounting aids to the
installation site.
• drop the unit, loosen the belts and pull away
the mounting aids.
A/C unit transport with mounting aids
2x metal angles
Size1-2
Size3-4