CyberAiR DX Floor Mounted IOM Manual
2.6.1.1
Floor Stand Height Adjustment
Standard and Low Seismic Floor Stands:
Standard Floor Stands- First loosen the middle hex nut (jam nut) on
each leg. Turn the top hex nut to raise or lower the floor stand. Lock
the height by tightening the middle hex nut up against the top hex nut.
FRONT LABEL
FLOOR STAND LEG
THREADED ROD TOP HEX
NUT
MIDDLE HEX NUT (JAM NUT)
Standard Floor Stand
BOTTOM HEX NUT (FIXED)
ISOLATION PAD
Low Seismic Floor Stands- First loosen the top hex nut (jam nut)
on each leg. Turn the entire foot weldment to raise or lower the
floor stand. Lock the height in place by tightening the top hex nut
up against the fixed hex nut in the floor stand leg.
ATTACHMENT
PLATES
QUANTITY
VARIES
Low Seismic Floor Stand
FLOOR STAND HEX NUT
(FIXED) TOP HEX NUT (JAM
NUT)
BOTTOM HEX NUT (FIXED)
ISOLATION PAD
High Seismic 4 - 10” Nominal Floor Stands:
High Seismic Floor Stands- First loosen the top hex nut (jam nut) on
each leg. Turn the entire foot weldment to raise or lower the floor
stand. Lock the height in place by tightening the top hex nut up against
the fixed hex nut in the floor stand leg.
ATTACHMENT
PLATES
QUANTITY
VARIES
High Seismic Floor Stand
4 - 10” Nominal
FLOOR STAND LEG
FLOOR STAND HEX NUT
(FIXED) TOP HEX NUT (JAM
NUT)
BOTTOM HEX NUT (FIXED) ISOLATION
PAD