steam humidifier iNstruCtiONs
Setting the capacity limitation “Sx%”
Use the potentiometer “Sx%” to set the capacity limitation in % of the maximum capacity (setting range:
25...100%, factory setting: 100%).
Setting the control signal
With the jumpers on jumper block “JP1” you can set the control signal. The control signal is adjusted on
0-10V, none of the jumpers „mA“, „SP“, „2P“ on jumper block „JP1“ may be set for this.
General unit settings
With the jumpers on the jumper blocks “JP1” and “JP2” you can set different unit parameters.
11.1.1.3 Configuration of the control unit eCCM/S
Pos.
with jumper
without jumper
Fi
Connection to a mains supply with ground fault circuit inter-
rupter **
Connection to a mains supply without ground
fault circuit interrupter
DRn
Increased drain operation factor
Regular drain operation factor **
CDY
Low water conductivity (<125 μS/cm)
Normal water conductivity (≥125 μS/cm) **
DSP
Exchangeable steam cylinder **
Cleanable steam cylinder
K
Fault No. 4 “steam cylinder maintenance due”:
the unit triggers a warning only (the error switch
on the control unit ECCM/S is not activated).
Fault No. 4 “steam cylinder maintenance due”:
72 hours after the warning an error is triggered and the
unit is switched off (red LED lights). However, the error
switch on the control unit ECCM/S is activated already
in warning status. **
L
Fault No. 3 “Fill time”: a warning is triggered after
20 minutes filling time exceeding. After 220 minutes filling
time exceeding an error is triggered and the unit is switched
off (red LED lights and the error switch on the control unit
ECCM/S is activated). **
Fault No. 3 “Fill time”: the unit directly triggers an
error after 20 minutes filling time exceeding (red
LED lights and the error switch on the control unit
ECCM/S is activated). However, the unit is switched off
after 220 minutes filling time exceeding.
Z, M, n
no function (spare)
** Factory settings
DAnGeR
Mortal danger by electric hazard
The steam humidifier OEM2 is operated with mains voltage. One may get in touch with live
parts when the unit is open. Touching live parts may cause severe injury or danger to life.
• Before carrying out any work set the steam humidifier OEM2 out of operation as described in
chapter 11.1.3.5 (switch off the unit, disconnect it from the mains and stop the water supply)
and secure the unit against inadvertent power-up.