3
© STULZ GmbH – all rights reserved EN/05.2017
raised floor stand
Other mounting options (e.g. louvers)
If louvers shall be installed beneath the unit, these must be first mounted onto the adapter plate.
• install the louver actuator on the shaft, so that it will later be on the right unit side in the proximity of the elec
-
tric cabinet.
Positioning of the A/C unit on the floor stand
When positioning the A/C unit on the floor stand, it must be brought precisely into the correct position above
the floor stand from the front (under no circumstances diagonally).
• use mounting aids to bring in the unit and
secure these by fixing belts at the A/C unit.
• lay at least two securing instruments (e. g.
square steel bars) on the stand to avoid a
slip-off.
• when the unit is in the right position take away
the securing aids and set down the unit.
• now pull away the mounting aids under the
unit.
when distance Z > 100 mm
when distance Z < 100 mm
Detail of raised floor connection
Raised floor stand
Adjustable support plate
Adjusting nut
Support pipe
Support base
Mafund plate
Raised floor cut out angle
Continuous seal profile
(use closed-cell material only)
Before unit installation
Raised floor plate
Angled bracket
Permanently elastic seal
Fixing
1
2
3
4
5
6
7
8
9
10
11
12
13
Mounting aid