Press Reset.
Press High Pressure Limit.
Press and hold the Pressure Relief button to relieve
pressure.
Reset the HPLS by pressing down on the Reset button.
The indicator turning green indicates proper function
of Low Water 1.
Repeat these steps for Low Water 2.
Attach air compressor fitting to the psi Test Hose.
Begin filling with air slowly until the High Pressure
Limit Switch trips (Trips around 15 psi).
Press the Operating Pressure button. Fill the boiler
again with compressed air until the Operating
Pressure Limit Switch trips (Trips around 14.5 psi).
Boiler Safety Test